General Information And Safety Warnings; Contents Of Delivery; Optional Accessories - Bicker UPSI-2403 User Manual

Dc ups system
Table of Contents

Advertisement

Available languages

Available languages

User's Manual UPSI-2403

1 General Information and Safety Warnings

Congratulations for choosing the UPSI-2403!
This manual explains the components and properties of the DC UPS UPSI-2403. All infor-
mation contained in this manual has been revised thoroughly to ensure accuracy and
completeness. Yet Bicker Electronic accepts no liability for any omissions or faults. We will
appreciate any notifications regarding faults, suggestions for improvements and criticism.
Saf et y Wa r nings
Installation and connection must only be carried out by qualified personnel.
The relevant rules of electrical engineering must be observed!
All connector cables must be dimensioned for the input current of the
UPSI-2403 (6.7 A) and an according additional protection must be provided and
fused. The recommended cross section for the connector cables is 1.5 mm
A polarity reversal can damage the UPS as well as the connected load.
Make sure sufficient convection is possible!
The service life of the batteries is app. 4...5 years at +20 °C and will decrease by half
with each temperature increase of 10 °C according to EUROBAT! The service life
depends also on temperature, discharge depth an the numbers of loading cycles.
During storage the UPS must be charged at least every 6 months.
To minimize the power consumption during storage, the fuses
must be removed.

1.1 Contents of Delivery

DC UPS UPSI-2403 with equipped 12 V / 1.3 Ah batteries
Pin-and-socket connector, Metz Connect, 5-pole
2 fuses 10 A Mini®Fuse

1.2 Optional Accessories

USB cable 2.0 / A/B connector / 500 mm (Article No. CB-USB01)