User Manual UPSI-IP-3 Series
UPS SYSTEM
IP65
Bicker Elektronik GmbH
Ludwig-Auer-Straße 23 | 86609 Donauwörth · Germany

Advertisement

Table of Contents
loading

Summary of Contents for Bicker UPSI-IP-3 Series

  • Page 1 English User Manual UPSI-IP-3 Series UPS SYSTEM IP65 Bicker Elektronik GmbH Ludwig-Auer-Straße 23 | 86609 Donauwörth · Germany...
  • Page 2 UPSI-IP-3 Series Legend of used symbols Symbol Description Attention! Important hazard warning. Do not dispose of in the domestic waste. Warning of electrical voltage. Revision Directory Date Change 21.09.2022 Initial version Revision 1-0 Revision 1-0...
  • Page 3 UPSI-IP-3 Series Revision 1-0...
  • Page 4: A Brief Specification Upsi-2406Ip-38Ac

    UPSI-IP-3 Series A Brief specification UPSI-2406IP-38AC 24 V / 6 A LiFePO4 INSIDE  Outdoor AC/DC UPS for extreme environments in robust aluminium housing with IP65 protection  Already integrated LiFePO4 energy storage (330 Wh) Temperature range -20…+50 °C ...
  • Page 5 UPSI-IP-3 Series Backup fuse B16 230 V AC 20 A / 120 V AC, IEC/EN Listed breaker, Type B <6 kA (Rated Short-Time-Withstand) Input and output cable AC input cable: Lapp ÖLFLEX® CLASSIC 100 BK 0,6/1 kV, 3x1.5mm² (incl. PE), length app. 3 m starting from chassis, open end DC output cable: Lapp ÖLFLEX®...
  • Page 6 UPSI-IP-3 Series Backup time* UPSI-2406IP-38AC Backupzeit [h] LFP-13250S 0...1A Backupzeit [h] LFP-13250S 0...1A Backupzeit [h] LFP-13250S 0...20W Backupzeit [h] LFP-13250S 0...20W Backupzeit [h] LFP-13250S 0...1A Backupzeit [h] LFP-13250S 0...20W Backupzeit [h] LFP-13250S 0...1A Backupzeit [h] LFP-13250S 0...20W Backupzeit [h] LFP-13250S 0...100W Backupzeit [h] LFP-13250S 0...100W...
  • Page 7 UPSI-IP-3 Series Derating UPSI-2406IP-38AC -20 -10 Ambient temperature [°C] Ambient temperature [°C] = 100…264 V AC = 90…99 V AC -20…0 °C: At sub-zero temperatures, the charging time increases according to the physical properties of the cells (increased internal resistance).
  • Page 8: Table Of Contents

    UPSI-IP-3 Series Brief specification UPSI-2406IP-38AC ..............4 Introduction and description ................9 B1 Description of the product and its functions ....................9 B2 Intended use – devices ............................10 B3 Intended use – connecting cables ........................ 10 Safety instructions ....................11 C1 Preventive measures and rules when operating the UPS system ..........
  • Page 9: B Introduction And Description

    The manual as well as all documents has to be read and followed strictly before installation. Otherwise in cer- tain situations warranty and guarantee can be cancelled partly or completely. Any liability on the part of Bicker Elektronik is excluded for possible existing errors as well as non-compliance with the instructions for use and installation.
  • Page 10: B2 Intended Use - Devices

    UPSI-IP-3 Series B2 Intended use – devices This device is primarily designed for use under difficult and extreme environmental conditions and can be used both indoors and outdoors. It has been developed for professional use in areas such as industrial control, communication and measurement technology.
  • Page 11: C Safety Instructions

    UPSI-IP-3 Series C Safety instructions WARNING! Disregarding of following issues can result in electric shock, fire, serious injury or death. 1. Care must be taken to ensure proper and professional connection of the device. 2. The device must not be exposed to fire and temperatures outside the specification.
  • Page 12: D Technical Data

    UPSI-IP-3 Series D Technical Data D1 General Technical Data INPUT DATA Input voltage 100…240 V AC nominal (±10 %), active PFC Input frequency 50…60 Hz nominal (±10 %) Inrush current <100 A (bei I = 220 V AC) Current consumption...
  • Page 13 UPSI-IP-3 Series OUTPUT DATA – NORMAL MODE Output voltage* 24 V DC Output voltage range* 24…23.4 V DC max. (depending on load) Capacitive load 3000 μF (at start, 0 A load) Output current 6…8 A DYN.BOOST 30 A (5 ms)
  • Page 14 UPSI-IP-3 Series ENERGY STORAGE Installed type BP-LFP-13250S Battery technology LiFePO4 Charging method CC / CV / CP 13.2 V Nominal voltage U End-of-charge voltage 13.8 V Battery charging current ≤0.2 C (4.5…5 A) Undervoltage protection As soon as the first cell reaches 2.5 V...
  • Page 15 UPSI-IP-3 Series DATA AC INPUT CABLE Type of cable ÖLFLEX® CLASSIC 100 BK 0,6/1 kV – conenction and control cable, 3G1,5 Article No. Lapp 1120463 Features Flame-retardant according to IEC 60332-1-2, UV and weather-resistant according to ISO 4892-2, ozone-resistant according to EN50396, coldflexible up to –30 °C Cable construction Fine wire strands of bare copper;...
  • Page 16 UPSI-IP-3 Series GENERAL DATA Flammability class according to UL 94 Weight 7.7 kg (device without cables) UPS connection in parallel UPS connection in series HOUSING Degree of protection IP 65 Protection class Mounting type Mast or surface mounting (or equal) Housing version Aluminium-cast housing, milled, FORMODAL®...
  • Page 17 UPSI-IP-3 Series INTERFERENCE IMMUNITY ACCORDING TO EN 62040-2 Uninterruptible Power Suppy Systems – Part 2: Electromagnetic compatibility requirements (EMC) Basic standard Fulfilled requirements according to EN 62040-2 Electrostatic discharge EN 61000-4-2 Contact discharge ±4 kV Air discharge ±8 kV Comment...
  • Page 18 Comment Class A *To improve the emitted interference, Bicker Elektronik recommends installing the "Würth 74272722" ferrite (not in scope of delivery) in the DC output cable of the UPS directly after the housing outlet (2 turns). HARMONIC CURRENTS ACCORDING TO EN 62040-2 Uninterruptible Power Supply Systems –...
  • Page 19: D2 Drawing

    62 mm 4 mm 18 mm E Name / Address / Support E-Mail / Phone number of the manufacturer Bicker Elektronik GmbH · Ludwig-Auer-Straße 23 · 86609 Donauwörth · Germany E-Mail: support@bicker.de · Tel.: +49 (0) 906 70595-0 Revision 1-0...
  • Page 20: F General Data

    UPSI-IP-3 Series F General Data F1 Assembly and installation advice The installation of devices that are not ready to be plugged in is to be carried out by the respec- tive network operator or by a registered specialist company, who will also assist in obtaining the approval of the respective network operator for the installation of the device.
  • Page 21: F3 Description Of Connectors

    UPSI-IP-3 Series F3 Description of connectors AC INPUT COLOUR FUNCTION BROWN L / phase conductor GREEN PE / protective earth YELLOW BLUE N / neutral conductor DC OUTPUT FUNCTION Vout + Vout – (GND) Revision 1-0...
  • Page 22: F4 Connection

    UPSI-IP-3 Series F4 Connection CONNECTING ORDER 1. DC OUTPUT (APPLICATION) 2. AC INPUT (SUPPLY NETWORK) Dismantling order reverse to connection! – ATTENTION! 1. Note correct colours and polarity! 2. Pay attention to the maximum cable length. The fixed input and output cables should not be lengthened because if the cables are too long, an unintentional power fail may be triggered (e.g.
  • Page 23 UPSI-IP-3 Series  WIRING DIAGRAM AC INPUT SOURCE INPUT: 100…240 V AC / 50…60 Hz OUTPUT: 24 V DC 24 V DC APPLICATION AC/DC- CONVERTER LOAD LOAD CHARGE 13.2 V DC BATTERY BATTERY PINOUT OF OUTPUT CABLE LiFePO4 4S1P UPSI-2406IP-38AC 1 = V+ 2 = V–...
  • Page 24: F5 Initial Operation

    UPSI-IP-3 Series F5 Initial operation The correct installation of the UPS has to be ensured. The device starts as soon as it is connected to AC voltage (100…240 V AC nominal) via the AC input line. The voltage is converted internally to 24 V DC and passed on to the UPS module. The energy storage device is que- ried and transmits its data.
  • Page 25: F8 Backup Time In Battery Mode

    UPSI-IP-3 Series F8 Backup time in battery mode The nominal backup times can be found within the technical data of this user manual or the user manual of the used energy storages. At extreme low or high temperatures a reduction of the nominal backup times can occur.
  • Page 26 UPSI-IP-3 Series Example 1 (UPSI-2406DP1 / UPSI-2406DP2) OUT Nominal Before second 0 After second 58 no load was taken. the device keeps Time [t] running, output remains free. E = 72 W · 4 sec + 120 W · 10 sec + 168 W · 12 sec + 192 W · 10 sec + 144 W · 4 sec + 192 W · 4 sec + 96 W · 4sec + 0 W · 8 sec + 120 W · 2 sec = 7392 Ws = 7.392 kJ ...
  • Page 27 UPSI-IP-3 Series Example 3 (UPSI-2406DP3) OUT Nominal After second 32 output is disconnected. Before second 0 already From second 0 4.90 kJ (4896 Ws) were taken for 4.46 kJ (4464 Ws) were taken for 26 seconds. further 32 seconds. Time [t] E = 120 W ·...
  • Page 28: F12 Status Led

    >> Output current too low, UPS is deactivated. >> Overcurrent at output (load current too high), output is deactivated >> Short circuit at output, output is deactivated >> Internal failure, UPS is deactivated. * Not available with UPSI-IP-3 series Revision 1-0...
  • Page 29: F13 Shutdown Diagram

    UPSI-IP-3 Series F13 Shutdown diagram False Power Fail True Ignition-Timer True Enabled False Shutdown SOC Max. Backup Shutdown-Timer Ignition Pin False Enabled Enabled OS Enabled High True True True True False False Shutdown SOC Max. Backup Shutdown-Timer Ignition Timer Threshold...
  • Page 30: F14 Recommendations For A Long Ups Service Life

    F17 Disclaimer We, the Bicker Elektronik GmbH, have checked the contents of this document for compliance with the hard- ware and software described. Nevertheless, deviations can not be ruled out, so we assume no liability for the complete agreement. The information in this publication is checked regularly, necessary corrections are inclu- ded in the updated versions.
  • Page 31 Bicker Elektronik GmbH Ludwig-Auer-Straße 23 86609 Donauwörth · Germany Tel. +49 (0) 906 70595-0 Note: Subject to errors and technical modifications! +49 (0) 906 70595-55 Windows® is a registered trademark of the Microsoft Corp. E-Mail info@bicker.de Status as at: 21.09.2022 – Revision 1-0...