F10 Backup Time In Battery Mode; F11 Behaviour In Case Of Exceeding Maximum Backup Time - Bicker UPSI-1208DP Series User Manual

Ups system din-rail
Table of Contents

Advertisement

UPSI-1208DPx

F10 Backup time in battery mode

The nominal backup times can be found within the technical data of this user manual or the user manu-
als / datasheets of the used energy storages. At extreme low or high temperatures a reduction of the nominal
backup times can occur.

F11 Behaviour in case of exceeding maximum backup time

When the given buffering times are exceeded, the output is separated on the basis of the discharge voltage of
the corresponding energy storage (total discharge protection).
With supercapacitors in particular, an additional switch-off threshold can take effect if the discharge current of
the energy storage device is too high (>15 A). This can occur at very high load currents at the output of the
UPS. The lower the voltage of the energy storage device decreases, the higher the discharge current so that a
constant power is ensured at the output of the UPS.
If the allowable output current during battery mode exceeds more than 70 %, the converter switches off first,
without separating the output immediately. In this case, the voltage at the output of the UPS can drop signifi-
cantly below 12 V. This condition should be avoided by shutting down the system in time.
26
Revision 1-5