Clearance To Combustibles; Floor Protection - Regency Fireplace Products Alterra F175B-2 Owners & Installation Manual

Freestanding wood fire
Hide thumbs Also See for Alterra F175B-2:
Table of Contents

Advertisement

INSTALLATION
Universal
Default (1)
A
475mm
*B
160mm
C
175mm
D
160mm
E
78mm
F
300mm
G
875mm
H
969mm
* Wall clearance taken from rear shield (not fan).

Floor Protection

A combustible floor must be protected by non-combustible material (like
tile, concrete board, or as defined by local codes) extending beneath
the heater as follows;
From Sides:
78mm (E)
From Front:
300mm(F)
From Back Shield:
160mm(D)
The floor protector should consist of 12mm thick cement fibre sheet
which has a thermal resistance of 0.8m
fibre sheet.
IMPORTANT
* (1) The Universal Default flue kit requires one 130
stainless reflective shield; fitted to the rear of the active flue.
* (2) The AHD Special Insulated flue kit must be installed with a
40mm air gap around the flue to any combustible surfaces and the
ceiling ring must be spaced as such to provide an air gap of 20mm
to the ceiling.
A 130º x 900mm stainless reflective must be fitted behind the active
flue.
The flue pipe shall extend not less than 4.6m above the top of the floor protector.
NOTE: Installation must be carried out by a licensed installer in accordance
with AS/NZS 2918:2001.
NOTE: A minimum clearance of 160mm (flat wall) or 175mm (corner wall) must be retained for all wall surfaces to allow for fan access and maintenance.
8
MINIMUM CLEARANCE TO
COMBUSTIBLE MATERIALS
AHD
Special (2)
475mm
160mm
175mm
160mm
78mm
300mm
875mm
969mm
k/w for 4mm sheets of cement
2
x 900mm
o
Regency Alterra Freestanding Wood Fire

Advertisement