 Auxiliary heater control 1
Operation
Heater on
Heater off
• Temperature of heater on (Thon): Adjustable by function number 62 (Operating temperature
switching of external heaters).
• All control temperatures will shift by adjusting "Thon".
Tr-Ts ≥ -1.8°F
(-1°C)
Tr-Ts ≥ -18°F
(-10°C)
A
*: When room temperature stays in this zone for a specific time, auxiliary heater is turned on. For
details, refer to function number 71.
Example: When set temperature (Ts) is 72°F (22°C) (Factory setting),
• and room temperature (Tr) increases above 53.6°F (12°C), signal output is on.
• and room temperature (Tr) increases above 69.8°F (21°C), signal output is off.
• and room temperature (Tr) decreases below 66.2°F (19°C), signal output is on.
• and room temperature (Tr) decreases below 50°F (10°C), signal output is off.
 Auxiliary heater control 2
Control that excludes "A" from
Operation
Heater on
Heater off
• Temperature of heater on (Thon): Adjustable by function number 62 (Operating temperature
switching of external heaters).
• All control temperatures will shift by adjusting "Thon".
Tr-Ts ≥ -1.8°F
(-1°C)
*: When room temperature stays in this zone for a specific time, auxiliary heater is turned off. For
details, refer to function number 71.
4-4. Details of function
Heater is on as shown in following diagram of heating temperature.
Heater is off as shown in following diagram of heating temperature.
Other than heating mode
Error occurred
Forced thermostat off
Fan stop protection
Tr-Ts
Off
Tr-Ts (=Thon) < -5.4°F (-3°C)
On
Tr-Ts < -21.6°F
Off
"Auxiliary heater control 1"
Heater is on as shown in following diagram of heating temperature.
Heater is off as shown in following diagram of heating temperature.
Other than heating mode
Error occurred
Forced thermostat off
Fan stop protection
Tr-Ts
Off
*
Tr-Ts (=Thon) < -5.4°F (-3°C)
On
Condition
*
Tr: Room temperature
Ts: Set temperature
Thon: Heater on temperature
(-12°C)
on page 05-37.
Condition
- (05-37) -
Tr: Room temperature
Ts: Set temperature
Thon: Heater on temperature