TABLE OF CONTENTS Unit Features & Benefits ................3-6 Selection Procedure ..................7 Model Identification Options ................8-9 General Data RKKB- Series ..................10-18 RKMB- Series ..................19-24 RKNB- Series ..................25-27 General Data Notes ..................28 Performance Data RKKB- Series ..................29-30 RKMB- Series....................31 RKNB- Series ....................32 Airflow Performance RKKB- Series ..................33-34 RKMB- Series ..................33-34...
( ) identifies the brand to the customer. a Rheem package unit arrives at the job, it is ready to go with a factory charge and quality checks. Each unit also proudly dis- plays the “Made in the USA” designation.
Page 4
0 to 6 turns open. occurs. There is a blower contactor Where the demands for the job require high static, Rheem has and compressor contactor for each high-static drives available that deliver nominal airflow up to 2" of compressor.
Page 5
The freeze stat protects on the market. The draft inducers ( ) draw the flame from the the compressor if the evapora- Rheem exclusive in-shot burners ( ) into the aluminized tubular tor coil gets too cold (below heat exchanger ( ) for clean, efficient gas heat.
Page 6
The condenser fan motor ( ) can easily be accessed and main- The Rheem roofcurb tained by removing the protective fan grille. The polarized plug ) is made for connection allows the motor to be changed quickly and elimi- toolless assembly at nates the need to snake wires through the unit.
SELECTION PROCEDURE EXAMPLE—RKKB/RKMB/RKNB- SERIES To select an RKKB- Cooling and Heating unit to meet a job 5. CALCULATE INDOOR BLOWER BTUH HEAT EFFECT requirement, follow this procedure, with example, using data FROM MOTOR WATTS, STEP 4. supplied in this specification sheet. BTUH = 4,717 x 3.412 = 16,094 1.
Page 8
B = “B Series Cabinet” Efficiency Designation K = Standard Efficiency ASHRAE 90.1-1989 Compliant M = High Efficiency ASHRAE 90.1-1999 Compliant N = Super High Efficiency EnergyStar Compliant Product Classification K = Rooftop—Commercial Tradebrand R = Rheem Packaged Gas/Electric [ ] Designates Metric Conversions...
Page 9
OPTIONS—RKKB/RKMB/RKNB- SERIES FACTORY INSTALLED OPTION CODES FOR RKKB, RKMB & RKNB Low Ambient Unwired Convenience Outlet Stainless Steel Option Code Time Delay Heat Exchanger Unfused Services Discount Freeze Stat No Options “x” indicates factory installed option. ECONOMIZER SELECTION FOR RKKB, RKMB & RKNB Single Enthalpy Economizer No Economizer With Barometric Relief...
GENERAL DATA—RKNB- SERIES NOM. SIZE 15 TON [52.8 kW] ENERGYSTAR COMPLIANT MODEL Model RKNB- Series A180CL25E A180CL35E A180CM25E A180CM35E Cooling Performance CONTINUED Gross Cooling Capacity Btu [kW] 180,000 [52.7] 180,000 [52.7] 180,000 [52.7] 180,000 [52.7] EER/SEER 11.5/NA 11.5/NA 11.5/NA 11.5/NA Nominal CFM/ARI Rated CFM [L/s] 6000/5500 [2831/2596] 6000/5500 [2831/2596]...
Page 26
GENERAL DATA—RKNB- SERIES NOM. SIZE 15 TON [52.8 kW] ENERGYSTAR COMPLIANT MODEL Model RKNB- Series A180DL25E A180DL35E A180DM25E A180DM35E Cooling Performance CONTINUED Gross Cooling Capacity Btu [kW] 180,000 [52.7] 180,000 [52.7] 180,000 [52.7] 180,000 [52.7] EER/SEER 11.5/NA 11.5/NA 11.5/NA 11.5/NA Nominal CFM/ARI Rated CFM [L/s] 6000/5500 [2831/2596] 6000/5500 [2831/2596]...
Page 27
GENERAL DATA—RKNB- SERIES NOM. SIZE 15 TON [52.8 kW] ENERGYSTAR COMPLIANT MODEL Model RKNB- Series A180YL25E A180YL35E A180YM25E A180YM35E Cooling Performance CONTINUED Gross Cooling Capacity Btu [kW] 180,000 [52.7] 180,000 [52.7] 180,000 [52.7] 180,000 [52.7] EER/SEER 11.5/NA 11.5/NA 11.5/NA 11.5/NA Nominal CFM/ARI Rated CFM [L/s] 6000/5500 [2831/2596] 6000/5500 [2831/2596]...
Page 28
GENERAL DATA—RKKB/RKMB/RKNB- SERIES NOTES: 1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm.
Page 29
SYSTEMS PERFORMANCE—RKKB- SERIES GROSS SYSTEMS PERFORMANCE DATA—A180 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C] CFM [L/s] 7200 [3398] 6000 [2831] 4800 [2265] 7200 [3398] 6000 [2831] 4800 [2265] 7200 [3398] 6000 [2831] 4800 [2265] DR ➀...
Page 30
SYSTEMS PERFORMANCE—RKKB- SERIES GROSS SYSTEMS PERFORMANCE DATA—A300 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C] CFM [L/s] 9580 [8400] 8400 [3964] 6720 [3171] 9580 [8400] 8400 [3964] 6720 [3171] 9580 [8400] 8400 [3964] 6720 [3171] DR ➀...
Page 31
SYSTEMS PERFORMANCE—RKMB- SERIES GROSS SYSTEMS PERFORMANCE DATA—A180 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C] CFM [L/s] 7200 [3398] 6000 [2831] 4800 [2265] 7200 [3398] 6000 [2831] 4800 [2265] 7200 [3398] 6000 [2831] 4800 [2265] DR ➀...
Page 32
SYSTEMS PERFORMANCE—RKNB- SERIES GROSS SYSTEMS PERFORMANCE DATA—A180 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C] CFM [L/s] 7200 [3398] 6000 [2831] 4800 [2265] 7200 [3398] 6000 [2831] 4800 [2265] 7200 [3398] 6000 [2831] 4800 [2265] DR ➀...
Page 35
ELECTRICAL DATA—RKKB- SERIES Unit Information Evaporator Fan Model No. Unit Operating Minimum Circuit Minimum Overcurrent Maximum Overcurrent Amps Amps RKKB- Volts Phase Voltage Range Ampacity Protection Device Size Protection Device Size (FLA) (LRA) A180CL25E 187-253 74/74 80/80 80/80 208/230 11.5 74.5 A180CL35E 187-253...
Page 37
ELECTRICAL DATA—RKMB- SERIES Unit Information Evaporator Fan Model No. Unit Operating Minimum Circuit Minimum Overcurrent Maximum Overcurrent Amps Amps RKMB- Volts Phase Voltage Range Ampacity Protection Device Size Protection Device Size (FLA) (LRA) A180CL25E 187-253 74/74 80/80 80/80 208/230 11.5 74.5 A180CL35E 187-253...
Page 39
ELECTRICAL DATA—RKNB- SERIES Unit Information Evaporator Fan Model No. Unit Operating Minimum Circuit Minimum Overcurrent Maximum Overcurrent Amps Amps RKNB- Volts Phase Voltage Range Ampacity Protection Device Size Protection Device Size (FLA) (LRA) A180CL25E 187-253 72/72 80/80 90/90 208/230 11.5 74.5 A180CL35E 187-253...
Page 41
UNIT DIMENSIONS—RKKB/RKMB/RKNB- SERIES GAS HEAT / ELECTRIC COOLING PACKAGE Illustration ST-A0886-06 BOTTOM VIEW Illustration [ ] Designates Metric Conversions ST-A0886-02...
Page 42
UNIT DIMENSIONS—RKKB/RKMB/RKNB- SERIES GAS HEAT / ELECTRIC COOLING PACKAGE SUPPLY AND RETURN DIMENSIONS FOR HORIZONTAL APPLICATIONS Illustration ST-A0886-05 DUCT SIDE VIEW SUPPLY AND RETURN DIMENSIONS FOR DOWNFLOW APPLICATIONS [60.3 mm] [533.4 mm] [508 mm] TYP. [968.4 mm] [112.7 mm] [52.4 mm] [146.1 mm] [3589.3 mm] SUPPLY AIR...
Page 43
UNIT DIMENSIONS—RKKB/RKMB/RKNB- SERIES UNIT DIMENSIONS GAS HEAT / ELECTRIC COOLING PACKAGE Illustration ST-A0886-03 Illustration ST-A0886-12 WEIGHTS Accessory Shipping—lbs [kg] Operating—lbs [kg] Capacity Tons [kW] Corner Weights by Percentage Economizer—Downflow 155 [70.31] 146 [66.22] Economizer—Horizontal 165 [74.80] 155 [70.31] 15-25 [52.8-87.9] Fresh Air Damper (Manual) 51 [23.13] 40 [18.14]...
Page 44
UNIT DIMENSIONS—RKKB/RKMB/RKNB- SERIES SLAB INSTALLATION Illustration ST-A0886-09 CLEARANCES The following minimum clearances are recommended for proper unit performance and serviceability. Recommended Location Clearance In. [mm] 48 [1219] A - Front 18 [457] B - Condenser Coil 18 [457] C - Duct Side *18 [457] D - Evaporator End 60 [1524]...
Page 46
ACCESSORIES ECONOMIZERS Use to Select Factory Installed Options Only RXRD-MFCM3—Single Enthalpy (Outdoor) RXRX-AV02—Dual Enthalpy Upgrade Kit RXRX-AR02—Optional Wall-Mounted CO Sensor Features Honeywell Controls Available Factory Installed or Field Accessory Gear Driven Direct Drive Actuator Fully Modulating (0-100%) Low Leakage Dampers Slip-In Design for Easy Installation Plug-In Polarized 12-pin Electrical Connections Pre-Configured—No Field Adjustments Necessary...
Page 47
ACCESSORIES ECONOMIZER FOR HORIZONTAL DUCT INSTALLATION Field Installed Only RXRD-NFCM3—Single Enthalpy (Outdoor) RXRX-AV02—Dual Enthalpy Upgrade Kit RXRX-AR02—Wall-mounted CO Sensor Features Honeywell Controls Available as a Field Installed Accessory Only Gear Driven Direct Drive Actuator Fully Modulating (0-100%) Low Leakage Dampers Slip-In Design for Easy Installation Plug-In Polarized 12-pin Electrical Connections Pre-Configured—No Field Adjustments Necessary...
Page 48
ACCESSORIES POWER EXHAUST KIT FOR RXRD-MFCM3(-), RXRD-NFCM3(-) ECONOMIZERS RXRX-BFF02 (C, D, or Y*) *Voltage Code VERTICAL AIRFLOW Illustration STA1000-02 HORIZONTAL AIRFLOW Illustration STA1000-01 High Speed ➀ Low Speed Model No. Volts Phase of Fans (ea.) CFM [L/s] ➁ CFM [L/s] ➁ (ea.) (ea.) RXRX-BFF02C...
Page 49
ACCESSORIES FRESH AIR DAMPER MOTORIZED DAMPER KIT RXRX-ATO1 (Motor Kit for RXRF-HEA1) Illustration ST-7951-17 RXRF-HEA1 (Manual) RXRX-ATO1 (Motorized damper kit for manual fresh air damper) Illustration ST-A0889-02 [ ] Designates Metric Conversions...
Page 50
ACCESSORIES ROOFCURBS (Full Perimeter) TYPICAL INSTALLATION Rheem’s new roofcurb design can be utilized on Illustration ST-A0888-02 15 and 25 ton [52.8 and 87.9 kW] models. One available height (14" [356 mm]). Quick assembly corners for simple and fast assembly. 1" [25.4 mm] x 4" [102 mm] Nailer provided.
The heating section shall have a tubular assembly includes direct drive gear driver, the indoor air section shall be insulated heat exchanger design using Rheem exclu- fully modulating 0-100 percent motor and with a cleanable foil faced, fire retardant sive burners and corrosion resistant steel...
Page 59
MECHANICAL SPECIFICATIONS—RKKB/RKMB/RKNB- SERIES Powered Exhaust—The field installed High Pressure Cutout—This factory or powered exhaust, available for all units, field installed option is offered for units that shall provide exhaust of return air, when do not have high pressure cutout as stan- using an economizer, to maintain better dard.
Page 68
FROM YOUR RETAILER. GENERAL TERMS OF LIMITED WARRANTY Rheem will furnish a replacement for any part of this product which fails in normal use and service within the applicable periods stated, in accordance with the terms of the limited warranty.