Rheem RHMV2421MNACJA Service Manual page 135

Duct type
Hide thumbs Also See for RHMV2421MNACJA:
Table of Contents

Advertisement

RP1736HJVXA
RP1748HJVXA
Normal defrost
Ta > = 14  F(-10 C) 4  F(-20 C) < = Ta <14  F(-10 C) Ta > = 4  F(-20 C) Tn = 21.2  F(-6 C)
<
<
°
°
Tn = 0.8xTa-11.6
Tn = 1.4  F(-17 C)
< =
Tn -18.4  F(-28 C)
Tn
: Outdoor condenser coil temperature.
Ta
: Outdoor temperature.
Tn-1 : Before 5 minutes detected Tn.
Sn
: Number of operation indoor units.
Sn-1 : Before 5 minutes detected Sn.
Heating operation start : Compressor ON
<
Tn = 0.8xTa-11.6
or
or
°
°
< =
°
Tn -18.4  F(-28 C)
Outdoor condenser coil temperature : Over 59
Compressor ON time : Maximum 15 minutes
<
Tn-Tn-1 < 28.4  F(-2 C)
°
°
and Sn=Sn-1
°
Defrost start
Defrost Indicator:
[Operation lamp]
7 sec ON / 2 sec OFF
3 sec. later Compressor : OFF
3 sec. later Outdoor fan motor : OFF
35 sec. later 4-way valve : OFF
41 sec. later Compressor : ON
or
Defrost end
04-27
Integrating defrost
Integrating defrost
(Integrating OFF count defrost)
More than 210 minutes
(For continuous operation)
Compressor OFF
Tn < 26.6  F(-3 C)
°
°
(and after 30 minutes,
count : 40 times
if the Tn < 26.6  F(-3 C)
°
°
(Less than 10 minutes)
or
Tn < 23  F(-5 C)
°
°
(and after 3 minutes,
if the Tn < 23  F(-5 C)
°
°
°
F(15°C)