Rheem RHMV2421MNACJA Service Manual page 77

Duct type
Hide thumbs Also See for RHMV2421MNACJA:
Table of Contents

Advertisement

Troubleshooting 20
Condenser coil liquid
temperature sensor error
Detective actuators:
Condenser coil liquid temperature thermistor
Detective details:
Condenser coil outlet or middle temperature
thermistor short or open detected
Forecast of cause:
1. Connector connection defective, open
2. Thermistor failure
3. Main PCB failure
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
OK
Check Point 2 : Check thermistor
Thermistor characteristics check (Disconnect thermistor from PCB and check.)
(PARTS INFORMATION 7)
OK
Check Point 3 : Check voltage of main PCB (DC5.0V)
Main PCB (CN65:1-3) voltage value = 5V (RP1724/1730HJVXA)
Main PCB (CN62:2-3) voltage value = 5V (RP1736/1748HJVXA)
Disconnect thermistor from main PCB, and check voltage.
RP1724HJVXA
RP1730HJVXA
If voltage does not appear, replace main PCB,
and execute check operation again.
RP1736HJVXA
RP1748HJVXA
1 2 3
1 2 3
CN65
Indicate or Display:
Indoor unit
Operation lamp: 7 times Flash,
Timer lamp
Wired remote control
Error code : [E : 73]
Outdoor unit (RP1736/1748HJVXA)
Mode Error
2
: Light OFF
1 2 3
1 2 3
CN62
03-27
: 3 times Flash
A
B
C
D
E
7
3
: Light ON
n : n times blinking
DC
F