Rheem RHMV2421MNACJA Service Manual page 140

Duct type
Hide thumbs Also See for RHMV2421MNACJA:
Table of Contents

Advertisement

2. CURRENT RELEASE CONTROL
RP1724HJVXA
RP1730HJVXA
The compressor frequency is controlled so that the outdoor unit input current does not exceeds
the current limit value that was set up with the outdoor temperature.
The compressor frequency returns to the designated frequency of the indoor unit at the time
when the frequency becomes lower than the release value.
Current release operation value / Release value
Heating
RP1724/1730HJVXA
OT
(Control / Release)
11.0A/ 10.5A
62.6°F(17°C)
13.0A/ 12.5A
53.6°F(12°C)
15.0A/ 14.5A
41°F(5°C)
15.0A/14.5A
Cooling
RP1724/1730HJVXA
OT
(Control / Release)
9.0A/ 8.5A
122°F(50°C)
10.0A/ 9.5A
114.8°F(46°C)
13.0A/ 12.5A
104°F(40°C)
14.5A/ 14.0A
53.6°F(12°C)
14.5A/ 14.0A
35.6°F(2°C)
14.5A/ 14.0A
04-32
OT : Outdoor temperature