Rheem RHMV2421MNACJA Service Manual page 115

Duct type
Hide thumbs Also See for RHMV2421MNACJA:
Table of Contents

Advertisement

7. HEATING OPERATION
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature,
and controls the operation frequency of the compressor.
* When room temperature is lower by 9°F (4.5°C) than a set temperature, compressor operation
frequency will attain to maximum performance.
* When room temperature is higher 1°F (0.5°C) than set temperature, compressor will be stopped.
* When room temperature is between +1° F(+0.5°C) to -9°F(-4.5°C) of the setting temperature,
the compressor frequency is controlled with
In heating operation
Maximum frequency is limited by airflow mode
RP1724HJVXA
RP1730HJVXA
RP1736HJVXA
RP1748HJVXA
in the range shown in Table 1.
High
Medium
Low
90 rps
55 rps
41 rps
90 rps
67 rps
59 rps
117 rps
04-07
Quiet
34 rps
54 rps

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents