Reset Command Interface; Display Current Parameter - Mitsubishi Electric MELSEC-F FX3U-J1939 User Manual

Hide thumbs Also See for MELSEC-F FX3U-J1939:
Table of Contents

Advertisement

FX
-J1939 User's Manual
3U
9.6

Reset Command Interface

This command can be used to reset the command interface and clear errors displayed in BFM #1000 to
#1066.
BFM No.
BFM #1000
BFM #1001 to #1066
9.7

Display Current Parameter

This command can be used to display the parameters in BFM #1001 to #1066 of the last executed CIF
command. If a command caused an error, this function allows the parameter which caused the error to be
displayed and to make the necessary adjustments to the parameters and the sequence program.
BFM No.
BFM #1000
BFM #1001 to #1066 Not used
TO (Write Access)
Command:
HFFFF (K-1)
Not used
TO (Write Access)
Command:
H0000
Description
FROM (Read Access)
H0000:
Execution complete
H0000
Description
FROM (Read Access)
H0000:
Input buffer is displaying.
Parameter values of the last executed CIF command
9 Command Interface
9.6 Reset Command Interface
For other response codes,
refer to Section 9.8
77
1
2
3
4
5
6
7
8
9
10