Cif: Error Code List - Mitsubishi Electric MELSEC-F FX3U-J1939 User Manual

Hide thumbs Also See for MELSEC-F FX3U-J1939:
Table of Contents

Advertisement

FX
-J1939 User's Manual
3U
9.8

CIF: Error code list

If an error occurs during the execution of a command, the CIF will display these errors and no further
commands will be accepted. To reset the CIF and clear the error, write HFFFF (K-1) to BFM #1000.
While processing a command in CIF, FX
The CIF cannot accept write access to BFM #1000 to #1066 during busy status.
1. When the error code is HFFFF or H000F in BFM #1000
Error Code
BFM #1000
HFFFF
H000F
2. When other error codes (except HFFFF and H000F) are in BFM #1000
Error Code
BFM #1000
BFM #1001 and following
HF00C
H0000:
H10FF
The corresponding
H12FF
parameter has no errors.
All other values:
H20FF
The corresponding
H30FF
parameter caused an error.
H31FF
Abort code
H100F
acknowledge code
*1.
For abort codes, refer to remote node's manual or J1939/ISO specification.
78
3U
BFM #1001
CIF is busy processing a command
H0000
This is the status message during CIF processing, not the error status.
The written command to BFM #1000 is an unknown command. Confirm the function mode
H0064
setting and the executed command.
Confirm the Message specific error code which stored is in BFM #1002.
H000F
Command is not allowed in current mode. Confirm the function mode setting and the
H0100
executed command.
H0200
Command is prohibited in online mode.
The command can not execute when the module is offline. Confirm the communication
H0F0F
status.
The command can not execute when the module is offline. Confirm the communication
status and error status.
HB0FF
HFFFF
Write access to CIF while CIF was busy.
At least 1 parameter in BFM #1001 to #1066 is invalid.
Invalid values are shown in the corresponding BFMs. BFMs with valid parameters are set
to H0000.
*1
or negative
Negative response:
This error is set in case a multi message transmission had to be terminated due to the
*1
received
reception of an abort or negative acknowledge message from a remote node.
from remote node
-J1939 displays HFFFF in the read access area of BFM #1000.
Description
For message specific error codes, refer to Section 5.19
For communication status, refer to Section 5.7
For communication status, refer to Section 5.7
Description
9 Command Interface
9.8 CIF: Error code list
For error status, refer to Section 12.2

Advertisement

Table of Contents
loading

Table of Contents