4.1.2

Applicable cable

Item
Cable Type
Unshielded/ Shielded
No. of Pairs
Conformance Standard
Wire Size
Impedance
*1.
Shielded twisted pair cable is recommended.
Note
The bus length, length related resistance and the cross section of the cable to be used should be related as
follows.
Bus Length (m) Length Related Resistance (mΩ/m)
0 to 40
40 to 300
300 to 600
600 to 1000
4.1.3

Termination of cable end

Strip 9 mm (0.35") of insulation from the end of the wire. For stranded
wires, terminate the end of the wire using a wire ferrule with insulating
sleeve.
Tighten the terminals to a torque of 0.4 to 0.5 N  m.
Do not tighten terminal screws with a torque outside the above-mentioned
range. Failure to do so may cause equipment failures or malfunctions.
• When using stranded wires
It may be difficult to insert the electric wire into the insulating sleeve
depending on the thickness of the electric wire sheath. Select the
electric wire by referring to the dimensions of the wire ferrule.
<Reference>
Manufacturer
Phoenix Contact
*1.
Old model name : CRIMPFOX ZA 3
*2.
Old model name : CRIMPFOX UD 6
4.1.4

Removal and installation of CAN bus connector

1) Removal
Evenly unscrew both CAN connector mounting screws, and remove the CAN connector from the module.
If the cable is attached to the connector, hold and pull the connector on the side. Do not pull the cable.
2) Installation
Place the CAN connector in the specified position, and evenly tighten both CAN connector mounting
screws.
Tightening torque 0.4 to 0.5 Nm
Do not tighten terminal block mounting screws with a torque outside the above-mentioned range.
Failure to do so may cause equipment failures or malfunctions.
SAE J1939-11, CAN (Layer 2)
Shielded
2
0.3 mm
Cross Section (mm
70
0.3 to 0.34 (AWG 22)
Less than 60
0.34 to 0.60 (AWG 22 to 19)
Less than 40
0.50 to 0.60 (AWG 20 to 19)
Less than 26
0.75 to 0.80 (AWG 18)
Model names
AI 0.5-8WH
AI-TWIN 2X 0.5-8WH
(or CRIMPFOX 6T-F
4.1 Applicable Cable and Connector
Applicable Cable
SAE J1939-15
Twisted pair cable
Unshielded
2 pair
ISO 11898/1993
2
to 0.82 mm
(AWG22 to 18)
120 
2
)
Insulating sleeve
2.6mm
(0.11")
Caulking tool
*1
CRIMPFOX 6
*2
)
4 Wiring
*1
9mm
(0.35")
Contact area
(Crimp area)
8mm
(0.32")
14mm(0.56")
29
1
2
3
4
5
6
7
8
9
10