INSTALLATION AND PREPARATION FOR USE
•
1.4.10.4 Restart after a long standstill period of time
After a seasonal standstill (1 to 6 months) or maintenance operations;
•
•
1.4.10.5 Stopping the compressor
The compressor can be stopped at any moment, however, consult the supplier if
further actions are required.
32
Refer to Section 1.4.10.2, Page 31.
Warning!
After a standstill period of time more than 1 month, pre-lubrication just
before starting is always obligatory. Refer Section 4.7, Page 61
Check settings of control and safety equipment.
Proceed to the complete starting procedure.
Warning!
Restarting compressor after a standstill period of time more than 6
months, consult your supplier. It is recommended to proceed with the
initial start up procedure.
0089288_imm_v_english_19
07.04.2021