Lubrication Data; Topping Up Oil With Compressor Operating; Evacuation, Leak Testing And Start-Up Of The Compressor/Package - GEA Grasso 5 Installation And Maintenance Instructions Manual

Reciprocating compressors for industrial refrigeration
Table of Contents

Advertisement

To shut down a compressor for long term periods, proceed as follows:
i.
ii.
iii.
iv.
Prior to starting up after a shut down, change the oil and exchange the oil filters.
Determine the starting and stopping procedure from prior to start the compressor.
2.4

LUBRICATION DATA

Determine max Toil and set this value in the safety device.
Change the oil as soon as an oil analysis indicates contaminated oil.
2.4.1

Topping up oil with compressor operating

Topping up oil is permitted during compressor operation.
Be sure that this oil is the same as in the plant (refer to Section 2.4, Page 35).
Without affecting the operation of the compressor, the oil may be topped up by
means of a separate oil pump. This pump enables the oil to be forced into the
crankcase via the oil charging valve, against suction pressure.
Fig.14:
2.5

EVACUATION, LEAK TESTING AND START-UP OF THE COMPRESSOR/PACKAGE

To evacuate the refrigeration system refer to Section 1.4.2, Page 24,
0089288_imm_v_english_19
07.04.2021
Tightly shut both the suction and discharge stop valves and the stop valve of
the oil return line (if present).
Disconnect the power source from the compressor drive motor and the
electrical control cabinet.
Place a moisture absorbing compound (eg a dessicant such as silica gel)
inside the control cabinet.
Place warning tags on the electric system and all closed stop valves.
Warning!
It is expressly pointed out that it is not permitted to mix different types
of oil. If another type of oil is used, first remove all the stale oil in the
filters, oil pump, crankcase, shaft seal, oil separator and oil drains of
the installation.
Hint!
Use Grasso's hand-operated oil pump, part. no. 18.13.121
Oil level in compressor sight glass
INSPECTION AND TROUBLE SHOOTING
LUBRICATION DATA
35