REPLACEMENT OF I/O MODULE
(14)Specifications comparison between A1SX41 (12VDC) and QX71
Specifications
Number of input points
Isolation method
Rated input voltage
Rated input current
Operating voltage range
Maximum number of
simultaneous input points
On voltage/on current
Off voltage/off current
Input resistance
Off  on
Response
time
On  off
Common terminal
arrangement
Operation indication
External connection
system
Applicable wire size
Current consumption
External dimensions
Weight
*1
Check the specifications of the sensor or switches to be connected to the QX71.
*2
The following shows the derating chart.
3
- 29
A1SX41
32 points
Photocoupler
12/24VDC
Approx. 3mA/Approx. 7mA
10.2 to 26.4VDC
(ripple ratio within 5%)
*2
Refer to the derating chart.
8VDC or more/2mA or more
4VDC or less/1mA or less
Approx. 3.3k
1ms/5ms/10ms/20ms/70ms or less
10ms or less
(24VDC)
1ms/5ms/10ms/20ms/70ms or less
10ms or less
(24VDC)
32 points/common
(common terminal: B1, B2)
On indication (LED)
40-pin connector
(accessory)
2
0.3mm
0.08A (typ. all points on)
130(H)×34.5(W)×93.6(D)mm
0.21kg
(A1SX41)
26.4VDC
: Compatible,
Compat-
QX71
32 points
Photocoupler
5/12VDC
5VDC Approx.1.2mA
12VDC Approx.3.3mA
4.5 to 6VDC
(ripple ratio within 5%)
10.2 to 14.4VDC
(ripple ratio within 5%)
Simultaneously on (100%)
3.5VDC or more/1mA or more
1VDC or less/0.1mA or less
Approx. 3.3k
(Configure the setting in the PLC
parameter dialog box.)
10ms is set by default.
(Configure the setting in the PLC
parameter dialog box.)
10ms is set by default.
32 points/common
(common terminal: B01, B02)
On indication (LED)
40-pin connector
(sold separately)
2
0.3mm
(A6CON1, A6CON4)
0.075A (typ. all points on)
98(H)×27.4(W)×90(D)mm
0.12kg
: Partially changed, : Incompatible
Precautions for replacement
ibility
The on voltage/on current differ.
The off voltage/off current differ.
Set the input response time of
parameter to the default value
(10ms).
Existing external wiring can be
used.
*1
*1