Mitsubishi Electric MELSEC Q Series Handbook page 68

Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

3
REPLACEMENT OF I/O MODULE
AnS/QnAS series model
Product
Interrupt module
A1SI61
Dummy module
A1SG62
Blank cover
A1SG60
Point
When using the extension base unit of the A/QnA series, please refer to the following for details.
Transition from MELSEC-A/QnA (Large Type) Series to Q Series Handbook (Fundamentals)
L(NA)08043ENG
3
- 15
Model
Model
1) External wiring: changed
2) Number of slots: not changed
3) Program
4) Specifications
QI60
5) Function: changed
[Dummy module function]
None
Consider using the QG60 and I/O assignment setting.
QG60
No restrictions
Q series alternative model
Remarks (restrictions)
Number of occupied I/O points: changed (32 points  16 points)
Rated input voltage: changed (12VDC is not applicable.)
Rated input current: changed (Approx.8mA Approx.6mA)
On voltage/on current: changed
Off voltage/off current: changed
Input resistance: changed
(condition setting: hardware switch  parameter)