Mitsubishi Electric MELSEC Q Series Handbook page 132

Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

3
REPLACEMENT OF I/O MODULE
(15)Specifications comparison between A1SY60E and QY68A
Specifications
Number of output points
Isolation method
Rated load voltage
Operating load voltage
range
Maximum load current
Maximum inrush current
Leakage current at off
Maximum voltage drop at
on
Off  on
Response
time
On  off
Surge suppressor
Common terminal
arrangement
Operation indication
Fuse rating
(breaking capacity)
Fuse blown indication
Voltage
External
power
Current
supply
External connection
system
Applicable wire size
Applicable solderless
terminal
Current consumption
External dimensions
Weight
*1
Connect a fuse to every external terminal to prevent the external device and module at load short from burnout.
Also, configure an external circuit if fuse blown indication is required.
3
- 79
A1SY60E
16 points
Photocoupler
5/12/24VDC
4.5 to 26.4VDC
(peak voltage 26.4VDC)
2A/point
(condition:
=L/R2.5ms),
4A/common
8A 10ms or less
0.1mA or less
0.2VDC (MAX.) 1A,
0.4VDC (MAX.) 2A
3ms or less
10ms or less (resistance load)
Zener diode
8 points/common
(common terminal: TB9, TB19)
On indication (LED)
7A
(1 fuse/common)
Cannot be changed.
(breaking capacity: 300A)
Available
(LED turns on when a fuse is blown
and a signal is output to the CPU
module.)
12/24VDC (10.2 to 26.4VDC)
10mA
(typ. 24VDC for each common)
20-point terminal block connector
(M3.57 screws)
2
0.75 to 1.25mm
R1.25-3.5, R2-3.5,
RAV1.25-3.5, RAV2-3.5
0.20A (typ. all points on)
130(H)34.5(W)93.6(D)mm
0.20kg
: Compatible,
QY68A
8 points
(16 points occupied)
Photocoupler
5-24VDC
4.5 to 28.8VDC
2A/point
8A/module
8A 10ms or less
0.1mA or less
0.3VDC (MAX.) 2A
3ms or less
10ms or less (resistance load)
Zener diode
All points independent common
On indication (LED)
None
(Connecting a fuse to external wiring
is recommended.)
-
-
18-point terminal block
(M36 screws)
2
Core: 0.3 to 0.75mm
(outside diameter: 2.8mm or less)
R1.25-3
(Sleeved solderless terminal cannot
be used.)
0.11A (typ. all points on)
98(H)27.4(W)90(D)mm
0.14kg
: Partially changed, : Incompatible
Compat-
Precautions for replacement
ibility
When 9 or more points are used,
use two QY68A modules.
Wiring of the terminal block
needs to be changed because all
terminals become independent.
*1
Fuses are not built in.
An external power supply is not
required.
Wiring change is required.
When two QY68A modules are
used, the current consumption is
increased. Review the current
capacity.
Wiring space is narrower.