Mitsubishi Electric MELSEC Q Series Handbook page 162

Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

4
REPLACEMENT OF POWER SUPPLY MODULE
(3) Specifications comparison between A1S62PN and Q62P
Specifications
Input power supply
Input frequency
Input voltage distortion
Max. input apparent
power
Inrush current
5VDC
Rated output
current
24VDC
5VDC
Overcurrent
protection
24VDC
5VDC
Overvoltage
protection
24VDC
Efficiency
Withstand voltage
Noise immunity
Insulation resistance
Power indicator
Fuse
Terminal screw size
Applicable wire size
Applicable solderless
terminal
Applicable tightening
torque
External dimensions
Weight
Allowable momentary
power failure period
Accessory
4
- 4
A1S62PN
100-240VAC+10%-15%
(85 to 264VAC)
±
50/60Hz
5%
Within 5%
105VA
20A within 8ms
3A
0.6A
3.3A or more
0.66A or more
5.5 to 6.5V
65% or more
Between batch inputs and LG and
batch outputs and FG
2830VAC rms/3 cycles (2000m)
• By noise simulator of 1500Vp-p
noise voltage, 1µs noise width,
and 25 to 60Hz noise frequency
• Noise voltage IEC801-4, 2kV
Between batch inputs and LG and
batch outputs and FG
10M or more by 500VDC insulation
resistance tester
LED indication
(Turns on when 5VDC is output.)
Built-in (unchangeable)
M3.5 7
2
0.75 to 2mm
RAV1.25-3.5, RAV2-3.5
59 to 88N·cm
130(H)  55(W)  93.6(D)mm
0.60kg
Within 20ms
None
: Compatible,
Q62P
100-240VAC+10%-15%
(85 to 264VAC)
±
50/60Hz
5%
Within 5%
105VA
20A within 8ms
3A
0.6A
3.3A or more
0.66A or more
5.5 to 6.5V
65% or more
Between batch inputs and LG and
batch outputs and FG
2830VAC rms/3 cycles (2000m)
• By noise simulator of 1500Vp-p
noise voltage, 1µs noise width,
and 25 to 60Hz noise frequency
• Noise voltage IEC61000-4-4, 2kV
• Between batch inputs and LG and
batch outputs and FG
• Between all inputs and LG
• Between all outputs and FG
10M or more by 500VDC insulation
resistance tester
LED indication
(normal: on (green), error: off)
Built-in (unchangeable)
M3.5 screws
2
0.75 to 2mm
RAV1.25-3.5, RAV2-3.5
66 to 89N·cm
98(H)  55.2(W)  90(D)mm
0.39kg
Within 20ms
None
: Partially changed : Incompatible
Compat-
Precautions for replacement
ibility
Tighten within the applicable
tightening torque.
Wiring space is narrower.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec-ans/qnas

Table of Contents