Pepperl+Fuchs Barcon PPC Operating Instructions Manual page 35

Pressure transmitter
Table of Contents

Advertisement

A sensor pass showing the sensor parameters is included with every instrument. These
must be changed if the electronic insert is replaced.
The following eleven pairs of values must be entered in matrix fields V2H7 and V2H8.
V2H7 sensor data No.
01
02
03
04
05
06
07
08
09
10
11
After entering the sensor parameters, the matrix fields V2H7 and V2H8 are released by
the code 333. All other matrix fields are then blocked against unauthorised operation.
Carry out the entry procedure as follows:
Moving through
#
Para.
the menus
Main group: Service
1
Locking operation
V9H9
Locking
Main group: Transmitter information
2
Enter sensor parameters
V2H7
Enter sensor
data No.
V2H8
Enter sensor
check sum
V2H7
Enter sensor
data No.
Enter all other pairs of values
V2H7
Enter sensor
data No.
V2H8
Enter sensor
coefficient A1
Main group: Service
3
Unlocking operation
V9H9
Unlocking
Note!
When entering the sensor parameters, the error code E101 "Sensor table check sum
error" is shown. The error message disappears when all sensor parameters are entered
correctly.
V2H8 sensor data value
Word 16 sensor check sum
HI Word 16 sensor serial number
LO Word 16 sensor serial number
HI Word 16 lower measurement limit
LO Word 16 lower measurement limit
HI Word 16 upper measurement limit
LO Word 16 upper measurement limit
HI Word 16 sensor coefficient A0
LO Word 16 sensor coefficient A0
HI Word 16 sensor coefficient A1
LO Word 16 sensor coefficient A1
Entry
333
01
e. g. 47769
02
11
e. g. 48112
e. g. 130
Barcon LHC/PPC (HART)
Maintenance and repair
Entering sensor
parameters
Note!
35