Barcon LHC/PPC (HART)
Operation
Position of the
operating elements
Function of the
Operating Elements
22
3.2
Function of the display
The digital display has two types of display:
•
Display in measurement mode: This is shown as standard
•
Display in calibration mode: This is shown after pressing the Zero or Span
key once. It returns automatically to measurement mode after 2 seconds
0,753
0 bar ... 1 bar
ú
Fig. 3.2: Function of the display
Display in measurement mode
4-character display of measured values and
input parameters
ó
bargraph of measured value
ì
lower range value
ö
upper range value
ú
nominal measuring range
3.3
Position and function of the operating elements on the electronic insert
Damping switch
Connection terminals for
measuring the signal current
Fig. 3.3: Position of the operating elements
No.
Operating element
Damping switch
ó
Key for calibrating the zero
point
ì
Key for calibrating the
measuring span
Key for calibrating the zero
point and key for
calibrating the measuring
point
Display in measurement mode
ó
Display in calibration mode
÷
Additional displays incalibration mode
÷
Display of the calibration point
(Z=Zero or S=Span)
ø
sets measuring range within the limits of the
measuring cel
Damping
Zero
Span
1
2
3
on
off
Display
+
–
Function
Switch position "off": Damping 0 s
Switch position "on": Damping 2 s.
This switch position also enables any damping to be entered between
0 s ... 40 s by remote communication e.g. with the handheld terminal.
press once: The acting pressure for the zero point is shown
press twice: The acting pressure for the zero point is adopted
press once: The acting pressure for the measuring span is shown
press twice: The acting pressure for the measuring span is adopted
press once simultaneously: The acting pressure is shown as the
bias pressure
press twice simultaneously: The acting pressure is adopted as the
bias pressure
0,753
ì
ö
S
0,250
Z
ø
ó
Key for zero point
calibration
ì
Key for measuring span
calibration