2.5

Electrical connection

Transposed, screened two-wire cabling is recommended for the connecting cable.
Max. wire diameter: 2.5 mm
The power supply voltage is:
Non-Ex: 11.5 V... 45 V DC
Ex i area: 11.5 V ... 30 V DC
Internal protection circuits against reverse polarity, HF interference and overvoltage
peaks.
A test signal can be measured using the terminal plugs for this purpose without
interrupting measurement.
Unscrew the cover
If present, remove the retainer ring with digital display. In addition:
- Push up the latch with the arrow until the grip of the retaining ring is
audibly released.
- Loosen the retainer ring carefully to prevent the display cable from
breaking. The plug of the display can remain plugged in.
Insert the cable through the cable entry
Connect the cable wires as shown in the connection diagram.
Where appropriate, replace the retainer ring with digital display.The grip of
the retainer ring clips in with an audible click.
Screw down the cover
To loosen the holder from the electronic
insert, push latch with arrow upwards.
Fig.2.11:
Lifting off the display and removing the retaining ring
Observe all local regulations for applications in the EEx i area!
Fig.2.12:
Graph showing load
2
permanently attached cable
R/Ω
1522
1000
840
500
0
11.5
20
30
45
U/V
Standard
EEx ia IIC T6