Commissioning And Operation Using Communication - Pepperl+Fuchs Barcon PPC Operating Instructions Manual

Pressure transmitter
Table of Contents

Advertisement

Barcon LHC/PPC (HART)
Commissioning
Preparatory work
Resetting to factory
settings (Reset)
Damping
Selecting the
pressure units
26
4.2

Commissioning and operation using communication

Wire up the Barcon (see chapter 2.5 "Electrical connection").
Decide which tool is to operate the Barcon and wire it up accordingly.
(see chapter 3.4 "Operation using PACTware®" and see chapter 3.5
"Operating with the HART protocol via universal HART communicator")
All used parameters are listed in the matrix of parameters (see chapter 8
"Matrix of parameters").
By entering a code, the entries in the Parameter are reset partially or completely to
factory settings. Further information on the various types of reset and their effects are
given in chapter 5.3 "Reset".
Moving through
#
Para.
the menus
Main group: Transmitter information
1
Resetting to factory settings (Reset)
V2H9
Default Values e. g. 2380 Enter
The damping affects the speed with which the output signal and the digital display
react to changes in pressure.
For setting the damping using the handheld terminal, the damping switch must be set to
"on". Values for damping between 0 s and 40 s can be selected using the handheld
terminal.
Moving through
#
Para.
the menus
1
Set the damping switch to "on"
Main group: Basic setting
2
Suppressing variations in the measured value
V0H7
Damping
output
= 0 s ... 40 s
Selecting the pressure units determines in which units the pressure-specific parameters
are to be shown. The pressure units available are given in the table below.
After selecting new pressure units all information on the pressure are converted into the
new units, e. g. 0 bar ...1 bar = 0 psi ... 14.5 psi.
Moving through
#
Para.
the menus
Main group: Basic setting
1
Selecting pressure units
V0H9
Selecting
pressure units
Units
Units
mbar
kPa
bar
MPa
Pa
mm H
O
2
hPa
m H
O
2
Entry
Entry
e. g. 20 s Enter
I
100 %
63 %
Entry
e. g. psi Enter
Units
in H
O
2
ft H
O
2
psi
2
g / cm
Damping switch
Damping
Zero
Span
1
2
3
on
off
Jump
Output
signal
τ
0
Units
Units
2
Torr
kg / cm
2
mm Hg
kgf / cm
atm
in Hg
2
lb / ft
time