Barcon LHC/PPC (HART)
Commissioning
Output on error
28
To indicate an error, an error code is transmitted with the measured value.
At the same time the bargraph in the digital display assumes the value selected by the
operator. The following values can be selected:
MIN: 3.6 mA
MAX: 22 mA
CONTINUE: measurement continued
Moving through
#
Para.
the menus
Main group: Basic settings
1
Selecting output on error
V0H8
Selecting fail-
safe
4.3

Locking/unlocking operation

After calibrating or entering all parameters, the operation can be locked by entering a
three-figure code other than 130. This blocks all fields and functions except V9H9
"Locking". Locking is released by entering 130.
Moving through the
#
para.
menus
Main group: Service
1
Locking operation
V9H9
Locking
2
Releasing locking
V9H9
Locking
I
Entry
e. g. MAX. Enter
Entry
e. g. 131 Enter
130 Enter
MAX. 22 mA
Continued measurement
MIN. 3.6 mA
t