Pepperl+Fuchs Barcon PPC Operating Instructions Manual page 20

Pressure transmitter
Table of Contents

Advertisement

Barcon LHC/PPC (HART)
Installation
Connecting the
handheld terminal
Connecting the
HART- Modem
for operating with
PACTware
20
Do not replace the battery of the handheld terminal in the explosion
hazardous area.
For a BARCON with FM or CSA certificate: Electrical connection according
to "Installation drawing" (enclosed in the packing of the Barcon).
For correct transmission of the communication signal, a minimum
resistance of 250
the power supply.
Damping
Zero
1
2
3
on
off
+
Fig.2.14:
The handheld terminal can be connected anywhere along the 4 mA ... 20 mA line.
The HART modem connects the Barcon with a HART protocol to the RS 232 C serial
interface of a personal computer. This enables the Barcon to be remotely operated with
operating program PACTware.
Damping
Zero
Span
1
2
3
on
off
Display
+
Fig.2.15:
The HART modem can be connected anywhere along the 4 mA ... 20 mA line.
must be present between the connection points and
Span
Display
4 mA ... 20 mA
Transmitterpower supply e. g. KFD2-STL3-Ex.1
4 mA ... 20 mA
Transmitter power supply e. g. KFD2-STL3-Ex.1
any device
I
O
I
O
min. 250 Ω
PC with PACTware
minimum
HART
Total resistance
modem
250