2.2
Main circuit terminals
 Terminal arrangement and wiring
FR-F860-00680, 01080

R1/L11 S1/L21
Charge lamp
Jumper
R/L1 S/L2 T/L3 N/-
P/+
P3
Jumper
Power supply
FR-F860-04420
Charge lamp
Jumper
R/L1 S/L2 T/L3
N/-
P/+
P/+
Power supply
DC reactor (option)

For the FR-F860-01080, a jumper is not installed across the terminals P1 and P/+. Always connect a DC reactor (FR-HEL), which is available as an option, across the
terminals P1 and P/+.

When an option other than the DC reactor must be connected to terminal P/+, use terminal P/+ (for option connection).
NOTE
• Make sure the power cables are connected to the R/L1, S/L2, T/L3. (Phase need not be matched.) Never connect the power cable to the U, V, W of the inverter. Doing
so will damage the inverter.
• Connect the motor to U, V, and W. Turning ON the forward rotation switch (signal) at this time rotates the motor counterclockwise when viewed from the load shaft.
(The phase sequence must be matched.)
• The charge lamp will turn ON when the power is supplied to the main circuit.
• When wiring the inverter main circuit conductor of the FR-F860-04420, tighten a nut from the right side of the conductor. When
wiring two wires, place wires on both sides of the conductor. (Refer to the drawing on the right.) For wiring, use bolts (nuts)
provided with the inverter.
FR-F860-01440 to 02430
R/L1
S/L2
PR
Power supply
M
Motor
M
Motor
R1/L11 S1/L21
Charge lamp
Jumper
T/L3
N/-
P/+
P/+
M
Motor
DC reactor (option)
Main circuit terminals
FR-F860-02890, 03360

R1/L11 S1/L21
Charge lamp
Jumper
R/L1 S/L2 T/L3 N/-
P/+
P/+
Power supply
DC reactor
P/+
(for option connection)
(option)
WIRING
M
Motor
7