 Details of the supported properties
• The details of the properties supported by the network port are as follows.
Property
Max Info Frames
Max Master
Object Identifier
Object Name
Object Type
Out Of Service
Status Flags
Property List
Reliability
Network Type
Protocol Level
Network Number
Network Number Quality
Changes Pending
APDU Length
Link Speed
MAC Address
IP Address
IP Subnet Mask
IP Default Gateway
IP DNS Server
BACnet MS/TP
Shows the maximum number of frames that
the inverter can transmit while it owns the
token. When a value is written, it is reflected to
the Pr.727 setting.
Shows the maximum address for master node
When a value is written, it is reflected to the
Pr.726 setting.
Shows the unique numeric code to identify the object.
Shows the object name.
Network Port: NETWORK_PORT (56)
FALSE (0)
Always 0.
Shows the property identifier list.
Shows the reliability of the network port.
Fixed to no-fault-detected (0) for the FR-F800(-E).
Shows the communication method of the
network.
Fixed to MSTP (2) for the FR-F800.
Shows the protocol level.
Fixed to BACNET_APPLICATION (2) for the FR-F800(-E).
Shows the network number.
Fixed to 0 for the FR-F800(-E). If a value other than "0" is written, an error code
VALUE_OUT_OF_RANGE (37) will be returned.
Shows the quality of the network port number.
Fixed to UNKNOWN (0) for the FR-F800(-E).
If the property value whose change is to be reflected at a reset is changed, TRUE is returned.
FALSE is returned after the status is initialized by a reset.
Shows the maximum number of octets.
Fixed to 50 octets for the FR-F800.
Shows the communication speed in the unit of
bit/s.
The Pr.332 setting value × 100 equals the
communication speed.
Shows the MAC address of the network port.
The Pr.331 setting value is used for the MAC
address.
For example, the MAC address is 7F when
Pr.331 = "127".
A rejection code (0) is displayed when the
property is read.
A rejection code (0) is displayed when the
property is read.
A rejection code (0) is displayed when the
property is read.
A rejection code (0) is displayed when the
property is read.
Details
A rejection code (0) is displayed when the
property is read/written.
A rejection code (0) is displayed when the
property is read/written.
Shows the communication method of the
network.
Fixed to IPV4 (5) for the FR-F800-E.
Shows the maximum number of octets.
Fixed to 1024 octets for the FR-F800-E.
Shows the communication speed in the unit of
bit/s.
The Pr.1426 setting value is used for the
communication speed.
A rejection code (0) is displayed when the
property is read/written.
Shows the octet string of the IP address
assigned to the inverter.
For example, C0A83200 is displayed when
the IP address is 192.168.50.0.
Shows the octet string of the subnet mask
assigned to the inverter.
For example, FFFFFF00 is displayed when
the subnet mask is 255.255.255.0.
Fixed to "00000000" for the FR-F800-E.
Fixed to "00000000" for the FR-F800-E.