• The Life alarm (Y90) signal turns ON when either the control circuit capacitor life, main circuit capacitor life, cooling fan life,
inrush current limit circuit life, internal air circulation fan life or the estimated residual life of the main circuit capacitor reaches
the level set to output the life alarm.
• For the terminal used for the Y90 signal, set "90" (positive logic) or "190" (negative logic) in any of Pr.190 to Pr.196 (Output
terminal function selection).
NOTE
• When using an option (FR-A8AY, FR-A8AR, FR-A8NC, FR-A8NCE), the life alarm for the Control circuit capacitor
life (Y86 signal), Main circuit capacitor life (Y87 signal), Cooling fan life (Y88 signal), Inrush current limit circuit life
(Y89 signal), and the estimated residual-life of the Main circuit capacitor (Y248 signal) can be output individually.
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the
other functions. Set parameters after confirming the function of each terminal.
3
Reset selection after inverter faults are cleared (Pr.349,
N241)
• When the communication option is specified for the command source in Network operation mode, it is possible to select
whether the inverter is reset after the "Fault reset" command is executed. (Only when the HMS network option is installed.)
Setting
Pr.349
N010
N240
0
0
0
1
1
0
100
0
1
101
1
1
1000
0
0
1001
1
0
1100
0
1
1101
1
1
*1
When 24 V external power is available for control circuit or power is input only to control circuit.
*2
Available when the HMS network option is installed.
Communication reset selection
N241
NET operation
mode
0
Reset enabled
0
Reset enabled
0
Reset enabled
0
Reset enabled
1
Reset enabled
1
Reset enabled
1
Reset enabled
1
Reset enabled
Description
Ready bit status selection
Other than NET
Main circuit:
operation mode
power-ON
Reset enabled
Ready bit: ON
Reset disabled
Ready bit: ON
Reset enabled
Ready bit: ON
Reset disabled
Ready bit: ON
Reset enabled
Ready bit: ON
Reset disabled
Ready bit: ON
Reset enabled
Ready bit: ON
Reset disabled
Ready bit: ON
2
Reset selection after
inverter faults are
cleared
Main circuit:
Reset
*1
power-OFF
Ready bit: ON
Enabled
Ready bit: ON
Enabled
Ready bit: OFF
Enabled
Ready bit: OFF
Enabled
*2
Ready bit: ON
Disabled
*2
Ready bit: ON
Disabled
*2
Ready bit: OFF
Disabled
*2
Ready bit: OFF
Disabled
BCN-C22005-895