2 Delivery and handling
Transport
The supply air module must be transported and stored
dry.
Assembly
SAM 42 is mounted free-standing on brackets, alternat-
ively above a VPB 200 (for VPB 300/VPBS 300 installa-
tion is carried out using brackets). Noise from the fan
can be transferred to the brackets.
• Install the brackets to an outside wall, ideally in a room
where noise does not matter, in order to eliminate
noise problems. If this is not possible, avoid placing
it against a wall behind a bedroom or other room
where noise may be a problem.
• Wherever the unit is located, walls to sound sensitive
rooms should be fitted with sound insulation.
• Route pipes so they are not fixed to an internal wall
that backs on to a bedroom or living room.
INSTALLATION AREA
Leave a free space of 800 mm in front of the supply air
module. All service on SAM 42 can be carried out from
the front.
SAM 42
800
NOTE
Ensure that there is sufficient space (300 mm)
above the supply air module for installing
ventilation hoses.
Supplied components
Support bushes
4 x
Compatible products
• F370
• F750
Chapter 2 | Delivery and handling
Vent hose
1 x
7