Burner Start-Up Cycle Diagnostics; Operating Fault Diagnostics - Riello P140 T/G Installation, Use And Maintenance Instructions

Light oil burners
Table of Contents

Advertisement

BURNER START-UP CYCLE DIAGNOSTICS

During start-up, indication is according to the followin table:
Sequences
Pre-purging
Ignition phase
Operation, flame ok
Operating with weak flame signal
Electrical supply lower than ~ 170V
Lock-out
Extraneous light
 Off
Key:

OPERATING FAULT DIAGNOSTICS

The control box has a self-diagnostic system, which easily allows identifying the operating faults (RED LED signal).
ITo use this function, wait at least ten seconds from the safety lock out, and then press the reset button for a minimum of 3 sec-
onds.
After releasing the button, the RED LED starts flashing as shown in the diagram below.
RED LED on
wait at least 10 s
The pulses of the LED constitute a signal spaced by approximately 3 seconds.
The number of pulses will provide the information on the possible faults, according to the table below:
SIGNAL
2 flashes
3 flashes
4 flashes
7 flashes
8 flashes
10 flashes
2915905
COLOUR CODE TABLE
 Yellow
Press button
for > 3 s
The flame does not stabilise at the end of the safety time:
– faulty photocell;
– faulty or soiled oil valves;
– neutral/phase exchange;
– faulty ignition transformer
– poor burner regulation (insufficient gas oil).
Min. air pressure switch (if installed) does not close:
– air pressure switch faulty;
– air pressure switch incorrectly regulated;
– max. air pressure switch triggered (if installed).
Min. air pressure switch (if installed) does not open or light in the chamber before firing:
– air pressure switch faulty;
– air pressure switch incorrectly regulated.
Loss of flame during operations:
– poor burner regulation (insufficient gas oil);
– faulty or soiled oil valves;
– short circuit between photocell and earth.
– Oil enabling thermostat fault;
– Break in heating elements.
– Wiring error or internal fault;
– Presence of electromagnetic disturbance: use the radio disturbance protection kit





 Green
 Red
Interval
Signal
3 s
PROBABLE CAUSE
12
Colour code


Signal

Advertisement

Table of Contents
loading

This manual is also suitable for:

476 t803476885