Burner Start-Up Cycle Diagnostics - Riello 885 T80 Installation, Use And Maintenance Instructions

Forced draught gas burner
Table of Contents

Advertisement

Available languages

Available languages

Safety component
Flame control
Flame sensor
Gas valves (solenoid)
Pressure switches
Pressure adjuster
Servomotor (electronic cam) (if present)
Oil valve (solenoid)
(if present)
Oil regulator (if present)
Oil pipes / couplings (metallic) (if present)
Fan impeller
(A)
Life cycle
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
15 years
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years
10 years or 500,000 start-ups
16
SAFETY TEST - WITH GAS BALL VALVE
CLOSED
It is fundamental to ensure the correct execution
of the electrical connections between the gas so-
lenoid valves and the burner to perform safely
the commissioning.
For this purpose, after checking that the connec-
tions have been carried out in accordance with
the burner's electrical diagrams, an ignition cycle
with closed gas ball valve -dry test- must be per-
formed.
1
The manual ball gas valve must be closed
2
The electrical contacts of the burner limit
switch need to be closed
3
Ensures closed the contact of the low gas
pressure switch
4
Make a trial for burner ignition
The start-up cycle must be as follows:
starting the fan for pre-ventilation
Performing the gas valve seal control, if pro-
vided
Completion of pre-ventilation
Arrival of the ignition point
Power supply of the ignition transformer
Electrical Supply of solenoid gas valves
Since the manual gas ball valve is closed, the
burner will not light up and its control box will go
to a safety lockout condition.
The actual electrical supply of the solenoid gas
valves can be verified by inserting a tester,
Some valves are equipped with light signals (or
close/open position indicator) that turn on at the
same time as their power supply.
IF THE ELECTRICAL SUPPLY OF THE
GAS
VALVES
OCCURS
UNEXPECTED TIMES. DO NOT OPEN
MANUAL GAS BALL VALVE, SWITCH
OFF POWER LINE; CHECK THE
WIRES; CORRECT THE ERRORS AND
REPEAT THE COMPLETE TEST.
SAFETY COMPONENTS
The safety components must be replaced at the
end of their life cycle indicated in Tab, (A). The
specified life cycles do not refer to the warranty
terms indicated in the delivery or payment con-
ditions.