Technical Data; Electrical Data - Riello P140 T/G Installation, Use And Maintenance Instructions

Light oil burners
Table of Contents

Advertisement

TECHNICAL DATA

Thermal power - Output
Operation
Fuel

ELECTRICAL DATA

Electrical supply
Motor
Ignition transformer
Absorbed electrical power
1 - Suction line
2 - Pump pressure adjustment screws
3 - Return line
4 - Manometer plug (G 1/8)
5 - Vacuometer plug (G 1/2)
6 - Reset push-button of the motor overload relay
7 - Wiring terminal board
8 - Control box reset push-button and lock-out lamp
Cable clamps
9 -
10 - Ignition transformer
Boiler front plate
drilling
* It is possible with a space upon request.
2915905
355 / 1660 kW - 30 - 140 kg/h (see page 2)
st
nd
1
stage - 2
stage - 3
Light oil, max. viscosity at 20° C: 6 mm
MOTOR IE1
Three-phase 220V +10% -10% ~ 60Hz without neutral
380V +10% -10% ~ 60Hz with neutral
10 A / 220V - 5.8 A / 380V
Primary: 2 A - Secondary: 2x 6.5 kV - 35 mA
4.5 kW
Fig. 1
DIMENSIONS (mm)
rd
stage
2
/s (1.5° E)
10 A / 230V - 5.8 A / 400V
4.1 kW
Quantity
2
2
4
1
4
11 - Regulating bush for combustion head
12 - Valves group with hydraulic jacks
13 - Electric board
Burner
1
MOTOR IE2
Accessories
Flexibles tubes
Nipples
Screws
Gasket for flange
Cable clamps