Technical Specifications

This section details the specifications and operating conditions of the device.
5.1

Power Supply Specifications

The RUGGEDCOM M2200F can be equipped with the following power supplies:
Electrical hazard – risk of damage to the device
Make sure power input to the device is within the specified input range.
HI (125/250 VDC)
HI (110/230 VAC)
a
(F) denotes fast-acting fuse
b
(T) denotes time-delay fuse.
c
Power consumption varies based on configuration. 10/100Base-TX ports consume roughly 1 W less than
fiber optic ports.
d
The HI power supply is the same power supply for both AC and DC.
5.2

Failsafe Relay Specifications

Max Switching Volt-
age
Rated Switching Cur-
rent
Maximum Switching
Capacity
5.3

Supported Networking Standards

Standard
IEEE 802.3u
RUGGEDCOM M2200F
Installation Manual, 01/2020, C79000-G8976-1343-06
CAUTION
Power Sup-
ply Type
Minimum
24 VDC
10 VDC
48 VDC
36 VDC
d
88 VDC
d
85 VAC
240 VAC, 125 VDC
2 A @ 240 VAC, 0.15 A @ 125 VDC, 2 A @ 30 VDC
150 W, 500 VA
10 Mbps Ports
 
Input Range
Maximum
36 VDC
72 VDC
300 VDC
264 VAC
100 Mbps
1000 Mbps
Ports
Ports
 
ü
Internal Fuse
Maximum Power
a b
Rating
Consumption
6.3 A(F)
28 W
3.15 A(T)
2 A(T)
2 A(T)
Description
100BaseTX/100BaseFX
5
c
25