Hmi Operation Levels; User Level; Menu Groups Of The User Level - ABB REF 610 Operator's Manual

Feeder protection relay
Hide thumbs Also See for REF 610:
Table of Contents

Advertisement

REF 610
REF 610
Main Menu
MEASUREMENTS
RECORDED DATA
OPERATION
SETTINGS
CONFIGURATION
INFO
Fig. 4.1.12.-1
Selecting the communication protocol for the rear connection
4.2.
4.2.1.
4.2.1.1.
26
Feeder Protection Relay
Operator's Manual - ANSI Version
1. Press an arrow button to access the main menu.
2. Use the arrow buttons to select CONFIGURATION\COMMUNICATION\REAR
PROTOCOL and press
example SPA).
3. Press
to enter the setting mode. The second line starts to flash.
4. Use
or
5. Press
to confirm the selection.
6. Press
to return the display to the idle mode.
Group Menu
CONFIGURATION
FUNCTION TEST/DI
COMMUNICATION
LANGUAGE
MEMORY SETTINGS
FREQUENCY
HMI PASSWORDS
TIME
TRIP CIRCUIT SUP
STORE COUNTER

HMI operation levels

The HMI menu consists of a user level and a technical level. The user level is used
for measuring and monitoring. The technical level is used for advanced protection
relay setting and can be configured to require a password. The password is required
after the default value 999 is replaced.

User level

Menu groups of the user level

The user level contains the following menu groups. You can monitor the data
without a password.
MEASUREMENTS
*
Monitored measured values
*
RECORDED DATA
*
. The cursor is at the setting currently in use (for
to select the wanted setting.
Parameter Menu
CONFIGURATION
REAR CONNECTION
REAR PROTOCOL
REAR COM. MODULE
SPA SETTINGS
IEC103 SETTINGS
MODBUS SETTINGS
UNIT ADDRESS
:xxx
COUNTER
:xxx
LINE-IDLE STATE
CONNECTION TYPE
CONFIGURATION
SPA
Confirm
IEC 60870-5-103
MODBUS RTU
MODBUS ASCII
Cancel
COM. MODULE
1MRS755539
A040244_2