Monitoring The Operation Data By The Remote Controller - Mitsubishi Electric PUZ-M200YKA Service Manual

Split-type, heat pump air conditioners
Hide thumbs Also See for PUZ-M200YKA:
Table of Contents

Advertisement

12

MONITORING THE OPERATION DATA BY THE REMOTE CONTROLLER

12-1. HOW TO "MONITOR THE OPERATION DATA"
Details on the operation data including each thermistor temperature and error history can be confirmed with the remote controller.
Select "Service" from the Main menu, and press the [
1
Select "Check" with the F1 or F2 button, and press the [
Select "Request code" with the F1 or F2 button, and press
the [
] button.
Set the Refrigerant address and Request code.
2
Select the item to be changed with the F1 or F2 button.
Select the required setting with the F3 or F4 button.
■ <Ref.address>setting [ 0 ] – [ 15 ]
■ <Request code>setting
Press the [
] button, Data will be collected and displayed.
OCH737
<PAR-4xMAA ("x" represents 0 or later)>
] button.
] button.
Request code: 004
Discharge temperature: 69˚C
91
Check menu
Error history
Diagnosis
Smooth maintenance
Request code
Service menu:
Cursor
F1
F2
F3
F4
Request code
Ref.address
Request code
Request:
Cur.
F1
F2
F3
F4
Request code
Ref.address
Request code
Request:
Cur.