<Outdoor unit operation monitor function>
[When optional part 'A-Control Service Tool (PAC-SK52ST)' is connected to outdoor controller board (CNM)]
Digital indicator LED1 displays 2 digit number or code to inform operation condition and the meaning of check code by
controlling DIP SW2 on 'A-Control Service Tool'.
Operation indicator
SW2: Indicator change of self-diagnosis
SW2 setting
ON
1
2 3 4 5 6
<Digital indicator LED1 working details>
(Be sure that the 1 to 6 in the SW2 are set to OFF.)
(1) Display when the power supply ON
When the power supply ON, blinking displays by turns.
Wait for 4 minutes at the longest.
(2) When the display lights (Normal operation)
1 Operation mode display
LED1
The tens digit: Operation mode
Display
Operation Mode
O
OFF/FAN
C
COOLING/DRY
H
HEATING
d
DEFROSTING
2 Display during error postponement
Postponement code is displayed when
compressor stops due to the work of
protection device.
Postponement code is displayed while
error is being postponed.
(3) When the display blinks
Inspection code is displayed when compressor stops due to the work of protection devices.
Display
Inspection unit
0
Outdoor unit
1
Indoor unit 1
2
Indoor unit 2
3
Indoor unit 3
4
Indoor unit 4
Display Contents to be inspected (When power is turned on)
63H connector(yellow) is open/TRS connector is open
F5
Indoor/outdoor communication error (Signal receiving error) (Outdoor unit)
E8
Indoor/outdoor communication error (Transmitting error) (Outdoor unit)
E9
Miswiring of indoor/outdoor unit connecting wire, excessive number of indoor units (4 units or more)
EA
Miswiring of indoor/outdoor unit connecting wire(reversed wiring or disconnection)
Eb
Startup time over
EC
Communication error except for outdoor unit
E0–E7
OCH737
Display detail
(Lighting)
The ones digit: Relay output
Display
0
1
2
3
4
5
6
7
8
A
Display
Contents to be inspected (During operation)
U1
Abnormal high pressure(63H operated)/High compressor temperature (TRS operated)
U2
Abnormal high discharge temperature and comp. surface thermistor, shortage of refrigerant
U3
Open/short circuit of discharge thermistor(TH4) and comp. surface thermistor (TH33)
U4
Open/short of outdoor unit thermistors (TH3, TH6, TH7 and TH8)
U5
Abnormal temperature of heat sink
U6
Abnormality of power module
Abnormality of superheat due to low discharge temperature
U7
Abnormality in outdoor fan motor
U8
Overheat protection
Ud
Compressor overcurrent interruption (When Comp. locked)
UF
Current sensor error
UH
Abnormal low pressure
UL
Compressor overcurrent interruption
UP
Abnormality of refrigerant
PL
Abnormality of indoor units
P1–Pb
Communication error of M-NET system
A0–A7
Explanation for display
1 second
interval
ON
1
Warming-up
Compressor
4-way valve
Compressor
ON
ON
ON
ON
ON
ON
72
Unit
SW2
(Initial setting)
2 3 4 5 6
Solenoid valve
ON
ON
ON
ON
ON
ON
ON
ON