Mitsubishi Electric PUZ-M200YKA Service Manual page 53

Split-type, heat pump air conditioners
Hide thumbs Also See for PUZ-M200YKA:
Table of Contents

Advertisement

• Before repair
Frequent calls from customers
Phone Calls From Customers
Unit does
1 The operating display of remote
not operate
controller does not come on.
at all.
2 Unit cannot be restarted for a
while after it's stopped.
3 Check code appears and blinks
on the display of remote
controller.
Remote
1 "Please Wait" is displayed
controller
on the screen.
2 "
" is displayed on the
screen.
3 "Heat Standby" is displayed on
the screen.
4 "Heat Defrost" is displayed on
the screen. (No air comes out of
the unit.)
OCH737
How to Respond
1 Check if power is supplied to air conditioner.
Nothing appears on the display unless power is
supplied.
2 Wait around 3 minutes to restart unit.
The air conditioner is in a state of being protected
by the microprocessor's directive. Once the
compressor is stopped, the unit cannot be
restarted for 3 minutes. This control is also applied
when the unit is turned on and off by remote
controller.
3 Check code will be displayed if any protection
devices of the air conditioner are actuated.
What is check code?
1 Wait around 2 minutes.
An automatic startup test will be conducted for
2 minutes when power is supplied to the air
conditioner. "Please Wait" will be kept displayed
while that time.
2 This indicates that it is time to clean the air filters.
Clean the air filters. "
the filter information of the maintanace menu.
See the operation manual that came with the
product for how to clean the filters.
3 This is displayed when the unit starts HEAT
operation, when the thermostat puts the
compressor in operation mode, or when the
outdoor unit ends DEFROST operation and
returns to HEAT operation.
The display will automatically disappear around
10 minutes later.
While "Heat Standby" is displayed on the remote
controller, the airflow amount will be restricted
because the indoor unit's heat exchanger is not
fully heated up. In addition to that, the up/down
vane will be automatically set to horizontal blow
in order to prevent cold air from directly blowing
out to human body. The up/down vane will return
to the setting specified by the remote controller
when "Heat Standby" is released.
4 The outdoor unit gets frosted when the outside
temperature is low and the humidity is high.
"Heat Defrost" indicates the DEFROST
operation is being performed to melt this frost. The
DEFROST operation ends in around 10 minutes
(at most 15 minutes).
During the DEFROST operation, the indoor unit's
heat exchanger becomes cold, so the fan is
stopped. The up/down vane will be automatically
set to horizontal blow in order to prevent cold air
from directly blowing out to human body. The
display will turn into "Heat Standby" when
DEFROST operation ends.
53
Refer to "SELF-DIAGNOSIS
ACTION TABLE".
Display time of "
" can be cleared from
depends on the model.
Long life filter: 2500 hrs.
Standard filter: 100 hrs.
Note
Check if servicing is
required for the error.
"