Air-Conditioners
PUZ-ZM•YKA Series
PUZ-M•YKA Series
English
INSTALLATION MANUAL
FOR INSTALLER
BH79D895W01_cover.indd
1
2020/08/25
16:15:33

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric Mr.SLIM PUZ-ZM-YKA Series

  • Page 1 Air-Conditioners PUZ-ZM•YKA Series PUZ-M•YKA Series English INSTALLATION MANUAL FOR INSTALLER BH79D895W01_cover.indd 2020/08/25 16:15:33...
  • Page 2: Table Of Contents

    This symbol mark is according to the directive 2012/19/EU Article 14 In ormation or users and Anne I . Your MITSUBISHI ELECTRIC product is designed and manufactured with high quality materials and components which can be recycled and reused. This symbol means that electrical and electronic equipment, at their end-of-life, should be disposed of separately from your household waste.
  • Page 3 1. Safety precautions • A ter installation has been completed, check or re rigerant leaks. I re riger- hen per orming bra ing work, be sure to ventilate the room su iciently. ant leaks into the room and comes into contact with the flame of a heater or Make sure that there are no ha ardous or lammable materials nearby.
  • Page 4: Installation Location

    1. Safety precautions 1.6. Accessories o outdoor unit (Fig. 1-1) (ZM200/250, M200/250) The parts show in the left are the accessories of this unit, which are affixed to the inside of the service panel. 1 Joint Pipe accessory ..×1 (1) Put flare nut which is removed from the Ball Valve on the Joint Pipe accessory and carry out flare work.
  • Page 5 2. Installation location 2.3. Outline dimensions (Outdoor unit) (Fig. 2-3) ZM200, 250 M200, 250 2.4. Ventilation and service space (mm) 2.4.1. indy location installation When installing the outdoor unit on a rooftop or other location unprotected from the wind, situate the air outlet of the unit so that it is not directly exposed to strong winds. Strong wind entering the air outlet may impede the normal airflow and a malfunction may result.
  • Page 6 2. Installation location /2.5. Minimum installation area If you unavoidably install a unit in a space where all four sides are blocked or there are depressions, confirm that one of these situations (A, B or C) is satisfied. Note: These countermeasures are or keeping sa ety not or speci cation guarantee. A) Secure sufficient installation space (minimum installation area Amin).
  • Page 7 2. Installation location Indoor units Install in a room with a floor area of Amin or more, corresponding to refrigerant quantity M (factory-charged refrigerant + locally added refrigerant). * For the factory-charged refrigerant amount, refer to the spec nameplate or installation manual. For the amount to be added locally, refer to the installation manual.
  • Page 8: Installing The Outdoor Unit

    3. Installing the outdoor unit (mm) • Be sure to install the unit in a sturdy, level surface to prevent rattling noises during operation. (Fig. 3-1) <Foundation specifications> Foundation bolt M10 (3/8") Thickness of concrete 120 mm Length of bolt 70 mm Weight-bearing capacity 320 kg...
  • Page 9 4. Installing the re rigerant piping 4.2. Connecting pipes (Fig. 4-1) 45°± 2 ° • When commercially available copper pipes are used, wrap liquid and gas pipes with commercially available insulation materials (heat-resistant to 100 °C or more, thickness of 12 mm or more). •...
  • Page 10 4. Installing the re rigerant piping 4.4. Re rigerant pipe airtight testing method (Fig. 4-5) (1) Connect the testing tools. • Make sure the stop valves A B are closed and do not open them. • Add pressure to the refrigerant lines through the service port C of the liquid stop valve A.
  • Page 11 4. Installing the re rigerant piping hen length e ceeds 70 m When the total length of the piping exceeds 70 m, calculate the amount of additional charge based on the following requirements. Note: If the calculation produces a negative number (i.e. a “minus” charge), of if calculation results in an amount that is less than the “Additional charge amount for 70 m”, perform the additional charge using the amount shown in “Additional charge amount for 70 m”.
  • Page 12: Drainage Piping Work

    4. Installing the re rigerant piping 4.7. Precautions when reusing e isting R22 re rigerant pipes • Refer to the flowchart below to determine if the existing pipes can be used and if it is necessary to use a filter dryer. •...
  • Page 13: Electrical Work

    6. Electrical work 6.1. Outdoor unit (Fig. 6-1, Fig. 6-2) ZM200, 250 ZM200, 250Y 1 Remove the service panel. M200, 250 M200, 250Y 2 Wire the cables referring to the Fig. 6-1 and the Fig. 6-2. ► Except PEA-M200, 250 L1 L2 L3 N S1 S2 S3 A Indoor unit...
  • Page 14 6. Electrical work 6.2. Field electrical wiring Outdoor unit model ZM200, 250/M200, 250 Outdoor unit power supply 3N~ (3 ph 4-wires), 50 Hz, 400 V Outdoor unit input capacity Main switch (Breaker) 32 A Outdoor unit power supply 5 × Min. 4 Indoor unit-Outdoor unit Cable length 50m: 3×4 (Polar) / Cable length 80m: 3×6 (Polar) Indoor unit-Outdoor unit earth...
  • Page 15: Test Run

    7. Test run 7.1. Be ore test run A ter completing installation and the wiring and piping o the indoor and • The insulation resistance drops due to accumulation of refrigerant in the com- outdoor units, check for refrigerant leakage, looseness in the power supply pressor.
  • Page 16: Special Functions

    8. Special Functions 8.1. Low noise mode (on-site modi cation) (Fig. 8-1) By performing the following modification, operation noise of the outdoor unit can be CNDM Orange reduced by about 3-4 dB. Brown Fig. 8-1 The low noise mode will be activated when a commercially available timer or the contact input of an ON/OFF switch is added to the CNDM connector (option) on the control board of the outdoor unit.
  • Page 17: Specifications

    10. Speci cations Outdoor model ZM200 ZM250 M200 M250 Power supply (V / Phase / Hz) 400 / Three / 50 Dimensions (W × H × D) 1050 × 1338 × 330 (+40) Cooling Sound level *1 dB (A) Heating *1 Measured under rated operation frequency.
  • Page 18 MITSUBISHI ELECTRIC, PUZ-M200YKA*, PUZ-M250YKA* PUZ-ZM200YKA*, PUZ-ZM250YKA* * : , , 1, 2, 3, · · · , 9 Note: Its serial number is on the nameplate of the product.
  • Page 19 <ENGLISH> <PORTUGUÊS> English is original. The other languages versions are translation of the original. O idioma original o ingl s. As vers es em outros idiomas s o tradu es do idioma original. CAUTION CUIDADO • Refrigerant leakage may cause suffocation. Provide ventilation in accordance with EN378-1. •...
  • Page 20 <POLSKI> <ROM N > J zykiem orygina u jest j zyk angielski. Inne wersje j zykowe stanowi Textul original este n limba englez . Versiunile pentru celelalte limbi sunt tradu- t umaczenie orygina u. ceri ale originalului. UWAGA ATENŢIE • Wyciek czynnika ch odniczego mo e spowodowa uduszenie. Nale y zapewni wentylacj zgodnie •...
  • Page 21 UNIT : mm Fig. 2-7 Fig. 2-8 Fig. 2-9 Fig. 2-10 Fig. 2-11 Fig. 2-12 Fig. 2-13 Fig. 2-14 Fig. 2-15 Fig. 2-16 Fig. 2-17 Fig. 2-18 Fig. 2-19 BH79D895W01_cover.indd 2020/08/25 16:15:35...
  • Page 22 This product is designed and intended for use in the residential, commercial and light-industrial environment. HEAD OFFICE: TOKYO BUILDING, 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN 9D 95W01 BH79D895W01_cover.indd 2020/08/25 16:15:35...