Mitsubishi Electric PUZ-M200YKA Service Manual page 79

Split-type, heat pump air conditioners
Hide thumbs Also See for PUZ-M200YKA:
Table of Contents

Advertisement

SW2 setting
Sub cool on error occurring SC
0 to 130
ON
Cooling = TH6−TH3
Heating = TH5−TH2
1
2 3 4 5 6
Thermo-ON time until error stops
0 to 999
ON
1
2 3 4 5 6
Indoor pipe temperature/Liquid (TH2 (3))
Indoor 3
ON
−39 to 88
1
2 3 4 5 6
Indoor pipe temperature/Cond./Eva. (TH5
(3))
ON
Indoor 3
−39 to 88
1
2 3 4 5 6
Outdoor temperature/Comp. Surface (TH33)
−52 to 221
ON
1
2 3 4 5 6
Controlling status of compressor
operating frequency
ON
1
2 3 4 5 6
OCH737
Display detail
79
The black square ( ) indicates a switch position.
Explanation for display
0 to 130
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
(Example) When 115°C;
0.5 s
0 to 999
(When it is 100 minutes or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 415 minutes;
0.5 s
−39 to 88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
−39 to 88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
When there is no indoor unit, "00" is displayed.
−52 to 221
(When the comp. surface thermistor detects 100°C or
more, hundreds digit, tens digit and ones digit are
displayed by turns.)
(Example) When 105°C;
0.5 s
The following code will be a help to know the
operating status of unit.
The tens digit
Display Compressor operating frequency control
1
Primary current control
Secondary current control
2
The ones digit (In this digit, the total number of
activated control is displayed.)
Display Compressor operating frequency control
Preventive control for excessive temp-
1
erature rise of discharge temperature
Preventive control for excessive temp-
2
erature rise of condensing temperature
4
Frosting preventing control
Preventive control for excessive temp-
8
erature rise of heat sink
(Example)
The following controls are activated.
• Primary current control
• Preventive control for excessive tempe-
rature rise of condensing temperature
• Preventive control for excessive tempe-
rature rise of heat sink
0.5 s
2 s
1
15
0.5 s
2 s
4
15
0.5 s
2 s
1
05
LED
1a
Unit
°C
Minute
°C
°C
°C
Code
display