Rear Vent Through-The-Wall Installations - Montigo Homefire Plus MD34-DV-2 Installation Operation & Maintenance

Modular gas fireplace
Hide thumbs Also See for Homefire Plus MD34-DV-2:
Table of Contents

Advertisement

Rear Vent Venting Runs
The MD34-DV-2 Rear Vent has three possible installations which do
not require vertical lift:
1. Straight Installation.
The height from the hearth to the center of the termination is 26
1/8". MD34-DV-2 Rear Vent versions are supplied with an 18"
extension pipe (EXT-18) with female/female connections. For
shorter installations, cut the EXT-18 to the desired length.
For extended installations, use the EXT-18 section as supplied
for an 18" vent run.
Note:
For Rear Vent models, maximum horizontal run with
no vertical lift must never exceed 18".
Heat Shield
EXT-18
Flue Collar
f i r e - p a r t s . c o m
Figure 15. Extended installation.
Part No. XG0106B
Installation
Termination
Rear Vent
2. 45° Corner Installation.
Attach an EEL-45 (45° elbow) directly onto the flue collar. Cut
the EXT-18 to suit, and attach it to the EEL-45. Slide the
fireplace into position and attach to the termination.
Figure 16. Corner installation.
3. Corner Installation - 45° or less.
Use an MTO-3 termination and an MFL-1 or MFL-18 (12" or
18" compressed length) and a frame, if appropriate. Flex may
be turned to obtain desired degree of angle required but must
not exceed 45°.
Figure 17. Flex installation.
Heat Shields
Due to high flue temperatures, heat shields are required on all MD34-
DV-2 installations (except those with vertical terminations) at the point
where the venting connects to the termination. With the heat shield, vent
clearances can be maintained at 1".
See Figure 8.
MD34-DV-2 Homefire
Termination
Heat Shield
EXT-18
EEL-45
Elbow
Flue Collar
Termination
Heat Shield
Flex
Section
Flue Collar
Page 9