Electrical Data - Bryant 581A/B Product Information Manual

Durapac and durapac plus series commercial single package rooftop units gas heating/electric cooling units
Table of Contents

Advertisement

VOLTAGE
NOMINAL
UNIT
RANGE
VOLTAGE
580F
(3 Ph, 60 Hz)
Min
Max
208/230
187
253
180
460
414
508
575
518
633
208/230
187
253
210
460
414
508
575
518 632.5 12.1
208/230
187
253
240
460
414
508
575
518
633
208/230
187.2 253
300
460
414
508
575
517.5 632.5
LEGEND
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM
— Indoor (Evaporator) Fan Motor
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC
— National Electrical Code
OFM
— Outdoor (Condenser) Fan Motor
RLA
— Rated Load Amps
*Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load
equipment (refer to NEC Articles 430 and 440), the overcurrent protective
device for the unit shall be fuse or HACR breaker. Canadian units may be
fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percent voltage
imbalance.

ELECTRICAL DATA

COMPRESSOR
No. 1
No. 1A
No. 2
RLA
LRA
RLA
LRA RLA LRA Qty Hp FLA (ea) Hp
32.1
195
20.7
156
16.4
95
10
12
80
8.2
30.1
225
28.8
195
15.5
114
14.7
80
10.7
42
239
33.6
225
19.2
125
17.3
114
13.8
80.0
13.5 80.0
20.7
156
20.7
156
47.1
245
10
75
10
75
19.6
125
8.2
54
8.2
54
15.8
100
OFM
IFM
FLA
3
0.5
1.7
5.0 15.8/15.8
70
3
0.5
0.8
5.0
7.9
54
3
0.5
0.75
5.0
6.0
3
0.5
1.7
5.0 15.8/15.8
95
3
0.5
0.8
5.0
7.9
80
3
0.5
0.75
5.0
6.0
2
1
6.6
7.5 25.0/25.0
2
1
3.3
7.5
13.0
2
1.0
3.4
7.5
10.0
6
0.5
1.7
10.0 28.0/28.0
6
0.5
0.8
10.0
14.6
6
0.5
0.8
10.0
13.0
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
EXAMPLE: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent voltage imbalance.
% Voltage Imbalance = 100 x
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, con-
tact your local electric utility company immediately.
192
POWER
COMBUSTION
EXHAUST
FAN MOTOR
FLA
LRA
FLA
0.57
4.6
18.8
0.57
0.30
2.3
6.0
0.30
0.57
2.1
4.8
0.57
0.57
4.6
18.8
0.57
0.30
2.3
6.0
0.30
0.57
2.1
4.8
0.57
0.57
4.6
18.8
0.57
0.30
2.3
6.0
0.30
0.57
2.1
4.8
0.57
0.57
4.6
18.8
0.57
0.30
2.3
6
0.30
0.57
2.1
4.8
0.57
average voltage
AB = 452 v
BC = 464 v
AC = 455 v
452 + 464 + 455
Average Voltage =
3
1371
=
3
= 457
7
457
POWER
SUPPLY
MCA
MOCP*
82/82
110/110
86/86
110/110
41
50
43
50
31
40
34
40
87/87
110/110
92/92
110/110
44
50
47
60
34
40
36
40
124/124 150/150
129/129 150/150
61
80
63
80
48
60
50
60
138/138 175/175
143/143 150/175
64
80
66
80
54
60
56
70