Bryant 581A/B Product Information Manual page 78

Durapac and durapac plus series commercial single package rooftop units gas heating/electric cooling units
Table of Contents

Advertisement

UNIT SIZE
NOMINAL
IFM
580F
V-PH-Hz
TYPE
STD
208/230-3-60
HIGH
STD
150
460-3-60
(12
1
/
Ton)
2
HIGH
STD
575-3-60
HIGH
STD
208/230-3-60
HIGH
STD
151
460-3-60
(12
1
/
Ton)
2
HIGH
STD
575-3-60
HIGH
LEGEND
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM
— Indoor (Evaporator) Fan Motor
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC
— National Electrical Code
OFM
— Outdoor (Condenser) Fan Motor
RLA
— Rated Load Amps
*Used to determine minimum disconnect per NEC.
†Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer
to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or
HACR breaker. Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use
the following formula to determine the percent of voltage imbalance.
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
average voltage
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage =
=
= 457
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
ELECTRICAL DATA (cont)
VOLTAGE RANGE
COMPRESSOR (each)
CONV
OUTLET
Min
Max
Qty
NO
YES
187
254
2
NO
YES
NO
YES
414
508
2
NO
YES
NO
YES
518
632
2
NO
YES
NO
YES
187
254
2
NO
YES
NO
YES
414
508
2
NO
YES
NO
YES
518
632
2
NO
YES
452 + 464 + 455
3
1371
3
OFM (each)
IFM
FLA
RLA
LRA
Qty
FLA
10.6
23
146
2
1.4
15.0
4.8
10.4
73
2
0.7
7.4
2.0
8.3
58.4
2
0.6
2.8
10.6
19
156
2
1.4
15.0
4.8
9
75
2
0.7
7.4
3.3
7.4
54
2
0.6
5.6
5.6
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local
electric utility company immediately.
3. For units with power exhaust: If a single power source is to be used, size wire to include
power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered
through the unit (must be in accordance with NEC and/or local codes). Determine the new
MCA including the power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust
For example, using a 580F060 unit with MCA = 28.9 and MOCP = 35, with
CRPWREXH030A01 power exhaust.
MCA New = 28.9 amps + 1.6 amps = 30.5 amps
If the new MCA does not exceed the published MOCP, then MOCP would not change. The
MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP is
acceptable. If "MCA New" is larger than the published MOCP, raise the MOCP to the next
larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.
POWER EXHAUST ELECTRICAL DATA
POWER EXHAUST
PART NO.
CRPWREXH030A01
CRPWREXH021A01
CRPWREXH022A01
CRPWREXH023A01
CRPWREXH028A01
CRPWREXH029A01
*Single or three phase.
78
COMBUSTION
POWER SUPPLY
FAN MOTOR
FLA
MCA
MOCP†
65.2
80
71.2
80
0.6
69.6
80
75.6
80
29.6
35
35.6
40
0.3
32.2
35
34.9
40
23.6
30
29.6
35
0.3
25.7
30
31.7
35
56.2
70
61.0
70
0.6
60.6
70
65.4
80
26.5
30
28.7
35
0.3
29.1
35
31.3
35
21.6
25
23.3
30
0.3
23.7
25
25.4
30
7
457
APPLICATION
MCA
MCA
MCA
USAGE
(230 V)
(460 V)
(575 V)
036-073*
1.6
N/A
0.64
036-073
N/A
0.68
N/A
090-151*
3.4
N/A
1.32
090-151
N/A
1.4
N/A
ALL*
1.7
N/A
0.68
ALL
N/A
0.7
N/A
MINIMUM UNIT
DISCONNECT SIZE*
FLA
LRA
68
383
74
387
73
406
79
410
31
192
34
194
34
203
37
205
25
154
27
156
27
163
29
165
59
359
65
364
64
378
70
383
28
174
30
176
31
213
33
215
23
127
25
129
25
159
27
160
MOCP
(separate
power source
only)
15
15
15
15
15
15