Bryant Preferred 581J 14 Series Installation Instructions Manual
Bryant Preferred 581J 14 Series Installation Instructions Manual

Bryant Preferred 581J 14 Series Installation Instructions Manual

Single package rooftop gas heat/electric cooling unit with puron (r-410a) refrigerant
Table of Contents

Advertisement

Quick Links

Preferred™ Series
581J*14
Single Package Rooftop Gas Heat/Electric Cooling Unit
®
with Puron
(R-410A) Refrigerant
581J units for installation in the United States contain use of Bryant's 2-speed indoor fan control system. This complies with
the U.S. Department of Energy (DOE) efficiency standard of 2018.
581J units for installation outside the United States may or may not contain use of the 2-speed indoor fan control system as
they are not required to comply with the U.S. Department of Energy (DOE) efficiency standard of 2018.
For specific details on operation of the Bryant 2-speed indoor fan system, refer to the Variable Frequency Drive (VFD)
Factory-Installed Option 2-Speed Fan Motor Control Installation, Setup, and Troubleshooting manual.
CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Rated Indoor Airflow (cfm) . . . . . . . . . . . . . . . . . . . . . . . . . 3
INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Jobsite Survey . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Step 1 - Plan for Unit Location . . . . . . . . . . . . . . . . . . . . . 6
Step 3 - Inspect Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Step 4 - Provide Unit Support . . . . . . . . . . . . . . . . . . . . . . 7
Step 5 - Field Fabricate Ductwork. . . . . . . . . . . . . . . . . . . 9
Step 6 - Rig and Place Unit. . . . . . . . . . . . . . . . . . . . . . . . . 9
(When Required). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Step 8 - Install Outside Air Hood . . . . . . . . . . . . . . . . . . 11
Step 9 - Install Flue Hood . . . . . . . . . . . . . . . . . . . . . . . . . 13
Step 10 - Install Gas Piping . . . . . . . . . . . . . . . . . . . . . . . 13
(GAS CONNECTION)
Step 12 - Make Electrical Connections . . . . . . . . . . . . . . 16
• UNITS WITHOUT FACTORY-INSTALLED NON-
FUSED DISCONNECT OR HACR CIRCUIT BREAKER
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53581014-01
Installation Instructions
Printed in U.S.A.
Form II581J-14-04
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
EconoMi$er® X (Factory Option). . . . . . . . . . . . . . . . . . . 27
Low Ambient Control (Factory Option) . . . . . . . . . . . . . . 40
cy Drive (Factory Option) . . . . . . . . . . . . . . . . . . . . . . . 40
RTU Open Control System . . . . . . . . . . . . . . . . . . . . . . . . 40
Smoke Detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Step 14 - Install Accessories. . . . . . . . . . . . . . . . . . . . . . . 41
Step 15 - Check Belt Tension . . . . . . . . . . . . . . . . . . . . . . 41
Pre-Start and Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . CL-1

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can be
hazardous due to system pressure and electrical components.
Only trained and qualified service personnel should install, re-
pair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions
of cleaning coils and filters and replacing filters. All other op-
erations should be performed by trained service personnel.
When working on air-conditioning equipment, observe precau-
tions in the literature, tags and labels attached to the unit, and
other safety precautions that may apply.
Follow all safety codes, including ANSI (American National
Standards Institute) Z223.1. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguisher available for all brazing operations.
It is important to recognize safety information. This is the safe-
ty-alert symbol
. When you see this symbol on the unit and
in instructions or manuals, be alert to the potential for personal
injury.
Pg 1
7-19
Replaces: II581J-14-03

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Preferred 581J 14 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Bryant Preferred 581J 14 Series

  • Page 1: Table Of Contents

    (R-410A) Refrigerant Installation Instructions 581J units for installation in the United States contain use of Bryant’s 2-speed indoor fan control system. This complies with the U.S. Department of Energy (DOE) efficiency standard of 2018. 581J units for installation outside the United States may or may not contain use of the 2-speed indoor fan control system as they are not required to comply with the U.S.
  • Page 2 Understand the signal words DANGER, WARNING, CAU- AVERTISSEMENT TION, and NOTE. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which RISQUE D’INTOXICATION AU MONOXYDE DE will result in severe personal injury or death. WARNING signi- CARBONE fies hazards which could result in personal injury or death.
  • Page 3: General

    GENERAL See Fig. 1-3 for unit options and dimensions. WARNING Rated Indoor Airflow (cfm) FIRE HAZARD Table 1 lists the rated indoor airflow used for the AHRI effi- Failure to follow this warning could result in personal inju- ciency rating for the units covered in this document. ry, death, and/or property damage.
  • Page 4 Fig. 2 — Unit Dimensional Drawing — 14 Size Unit...
  • Page 5 Fig. 2 — Unit Dimensional Drawing — 14 Size Unit (cont)
  • Page 6: Installation

    LOCATION DIMENSION CONDITION 48-in. (1219 mm) Unit disconnect is mounted on panel 18-in. (457 mm) No disconnect, convenience outlet option 18-in. (457) mm Recommended service clearance 12-in. (305 mm) Minimum clearance 42-in. (1067 mm) Surface behind servicer is grounded (e.g., metal, masonry wall) 36-in.
  • Page 7: Pad-Mounted Installation

    Install condensate line trap and piping Step 4 — Provide Unit Support Make electrical connections ROOF CURB MOUNT Install other accessories Accessory roof curb details and dimensions are shown in PAD-MOUNTED INSTALLATION Fig. 4. Assemble and install accessory roof curb in accordance Prepare pad and unit supports with instructions shipped with the curb.
  • Page 8 Fig. 4 — Roof Curb Details...
  • Page 9: Slab Mount (Horizontal Units Only)

    Step 5 — Field Fabricate Ductwork NOTE: Cabinet return-air static pressure (a negative condition) shall not exceed 0.35 in. wg (87 Pa) with economizer or 0.45 in. wg (112 Pa) without economizer. For vertical ducted applications, secure all ducts to roof curb and building structure.
  • Page 10: Positioning On Curb

    PLACE ALL SEAL STRIP IN PLACE BEFORE PLACING UNIT ON ROOF CURB. 36"-54" “B” (914-1371) “C” DUCT END DETAIL “A” “A” SEE DETAIL “A” DIMENSIONS MAX WEIGHT UNIT 581J*14 2215 1009 116.0 2945 62.5 1590 59.5 1510 NOTES: 1. SPREADER BARS REQUIRED — Top damage will occur if spreader bars are not used. 2.
  • Page 11: Step 8 - Install Outside Air Hood

    inserted into the notches on the basepan to properly seal. The SCREWS notches are covered by the tape used to secure the insulation to the basepan and are not easily seen. See Fig. 10 for position of the notches in the basepan. Seals around duct openings must be tight.
  • Page 12: Two Position Damper Hood Removal And Setup - Factory Option

    ECONOMIZER HOOD AND TWO-POSITION HOOD NOTE: If the power exhaust accessory is to be installed on the unit, the hood shipped with the unit will not be used and must be discarded. Save the aluminum filter for use in the power exhaust hood assembly.
  • Page 13: Step 9 - Install Flue Hood

    PANEL INDOOR COIL ACCESS PANEL SCREW LEFT HOOD SIDE CONTROL BOX ACCESS PANEL FLUE HOOD HOOD DIVIDER Fig. 16 — Economizer Hood Construction Fig. 18 — Flue Hood Details Step 10 — Install Gas Piping Installation of the gas piping must be in accordance with local building codes and with applicable national codes.
  • Page 14: Factory Option Thru-Base Connections

    Table 6 — Liquid Propane Manifold Pressure Ranges ” ELECTRICAL BULKHEAD ” ELECTRICAL CONNECTOR UNIT HIGH FIRE LOW FIRE BULKHEAD CONNECTOR 581J*14 10.0 in. wg (2490 Pa) 5.7 in. wg (1420 Pa) ” NPT GAS ADAPTER CAUTION FITTING EQUIPMENT DAMAGE Failure to follow this caution may result in equipment damage.
  • Page 15 9” (229mm) min Burner Access Panel Union Thru-Curb Adapter -in NPT THRU-BASE SUPPORT STREET GAS FITTING ELBOW BRACKET Fig. 22 — Gas Line Piping Unit Base Rail Other hardware required to complete the installation of the gas supply line will include a manual shutoff valve, a sediment trap (drip leg) and a ground-joint union.
  • Page 16: Step 11 - Install External Condensate Trap And Line

    NOTE: Pressure test the gas supply system after the gas supply piping is connected to the gas valve. The supply piping must be disconnected from the gas valve during the testing of the piping systems when test pressure is in excess of 0.5 psig (3450 Pa). Pres- sure test the gas supply piping system at pressures equal to or less than 0.5 psig (3450 Pa).
  • Page 17: Field Power Supply

    FIELD POWER SUPPLY For those units without through-the-curb power, conduit must be used to route the main power from the condenser end, via the power entry in the corner post of the unit (see Fig. 29 and 30) to either the factory option disconnect or the bottom of the control box.
  • Page 18: All Units

    (fuse or breaker) per NEC Article 440 (or local codes). cal components. Such operation would invalidate any ap- Refer to unit informative data plate for MOCP (Maximum plicable Bryant warranty. Over-current Protection) device size. NOTE: Units ordered with factory installed HACR do not need an...
  • Page 19: Units With Factory-Installed Non-Fused Disconnect

    To field install the NFD shaft and handle: Units Without Disconnect Remove the unit front panel (see Fig. 2). Remove (3) hex screws on the NFD enclosure - (2) on the Equip face of the cover and (1) on the bottom. GR Lug Remove the front cover of the NFD enclosure.
  • Page 20 Non-powered type This type requires the field installation of a general-purpose NOTICE/AVIS 125-v 15-A circuit powered from a source elsewhere in the building. Observe national and local codes when selecting wire Convenience Outlet Utilization size and conduit requirements, fuse or breaker requirements Maximum Intermittent Use 15 - Amps Maximum Continuous Use 8 - Amps and disconnect switch size and location.
  • Page 21: Factory Option Thru-Base Connections (Electrical Connections)

    Building Management System, or the RTU Open Multi-Proto- col Controller (RTU Open controller is available as a factory- installed option only). THERMOSTAT Install a Bryant-approved accessory 2-stage cooling/heating thermostat according to installation instructions included with ” ELECTRICAL the accessory. Locate the thermostat accessory on a solid wall...
  • Page 22: Unit Without Thru-Base Connection Kit

    thermostat cable or equivalent with minimum of six leads. on rise in space RH above control setpoint) or a combination Check the thermostat installation instructions for additional fea- thermostat-humidistat control device isolated contact set for de- tures which might require additional conductors in the cable. humidification control.
  • Page 23 Fig. 45 — 581J*14 Controls Wiring Diagram (208/230-v, 460-v, 575-v)
  • Page 24 Fig. 46 — 581J*14 Power Wiring Diagram (208/230-v, 460-v)
  • Page 25 Fig. 47 — 581J*14 Power Wiring Diagram (575-v)
  • Page 26 Fig. 48 — Typical Perfect Humidity™ Adaptive Dehumidification System Humidistat Wiring...
  • Page 27: Economi$Er® X (Factory Option)

    Programmable Thermostat Unit CTB THERMOSTAT O/W2/B SRTN Perfect Humidity™ FIOP *Connection not required. Fig. 49 — Typical Rooftop Unit with Perfect Humidity™ Adaptive Dehumidification System with Programmable Thermostat EconoMi$er X (Factory Option) ® SYSTEM COMPONENTS The EconoMi$er X system is an expandable economizer con- The EconoMi$er X system includes an economizer module, trol system, which includes a W7220 economizer module (con- 20k mixed air sensor, damper actuator, and either a 20k out-...
  • Page 28: Inputs

    • Relay Digital Output Rating at 30 vac (maximum power NOTE: The four terminal blocks are removable. Slide out each from Class 2 input only) — 1.5A run: terminal block, wire it, and then slide it back into place. 3.5A inrush at 0.45PF (200,000 cycles) or 7.5A inrush at 0.45PF (100,000 cycles) •...
  • Page 29: Interface Overview

    Table 9 — Economizer Module Table 10 — HH57AC081 Sensor Wiring Terminations (Right Hand Terminal Blocks) TERMINAL TYPE DESCRIPTION LABEL TYPE DESCRIPTION NUMBER LABEL Top Right Terminal Blocks S-BUS Communications AUX2 I 24 vac IN The first terminal is not used. S-BUS S-BUS (Enthalpy Control...
  • Page 30: Setup And Configuration

    To use the keypad when working with menus: Press the (Enter) button to accept the displayed value and store it in nonvolatile RAM. “CHANGE STORED” • Press the ▲ (Up arrow) button to move to the previous displays. menu. Press the (Enter) button to return to the current menu •...
  • Page 31 Table 12 — W7220 Menu Structure* (cont) PARAMETER PARAMETER EXPANDED PARAMETER NAME MENU PARAMETER DEFAULT RANGE AND Notes VALUE INCREMENT † SECOND STAGE COOLING DEMAND (Y2–IN) Y2–I signal from space thermostat or unitary controller for COOL Y2—IN ON/OFF second stage cooling. ON = 24 vac on terminal Y2–I OFF = 0 vac on terminal Y2–I SECOND STAGE COOLING RELAY OUTPUT...
  • Page 32 Table 12 — W7220 Menu Structure* (cont) PARAMETER PARAMETER EXPANDED PARAMETER NAME MENU PARAMETER DEFAULT RANGE AND Notes VALUE INCREMENT † 38°F to 70°F SUPPLY AIR SETPOINT (3°C to 21°C); MAT SET 53°F (12°C) The economizer will modulate the OA damper to maintain the increment by mixed air temperature at the set point 1 degree...
  • Page 33 Table 12 — W7220 Menu Structure* (cont) PARAMETER PARAMETER EXPANDED PARAMETER NAME MENU PARAMETER DEFAULT RANGE AND Notes VALUE INCREMENT † In CONV mode: SD = Enables configuration of shutdown (default); Shutdown (SD) W = Informs controller that system is in heating mode. Heat (W1) NOTE: If using 2-speed fan mode, you must program CONV AUX2 IN...
  • Page 34 Table 12 — W7220 Menu Structure* (cont) PARAMETER PARAMETER EXPANDED PARAMETER NAME MENU PARAMETER DEFAULT RANGE AND Notes VALUE INCREMENT † RETURN AIR HUMIDITY CALIBRATION RA H CAL 0% RH ±10% RH Allows for operator to adjust for an out of calibration humidity sensor.
  • Page 35 Table 12 — W7220 Menu Structure* (cont) PARAMETER PARAMETER EXPANDED PARAMETER NAME MENU PARAMETER DEFAULT RANGE AND Notes VALUE INCREMENT † ACTUATOR VOLTAGE HIGH ACT OVER V Voltage received by actuator is below expected range. ALARMS (cont) ACTUATOR STALLED ACT STALLED Actuator stopped before achieving commanded position.
  • Page 36 Table 15 — Dry Bulb Operation with DCV (CO Sensor) — 1 Speed Fan DEMAND OUTSIDE AIR CONTROLLED GOOD TO Y1-I Y2-I FAN SPEED Y1-O Y2-O OCCUPIED UNOCCUPIED VENTILATION (DCV) ECONOMIZE High 0-v/Off 0-v/Off Closed VENTMIN High 24-v/On 0-v/Off Closed VENTMIN High 24-v/On...
  • Page 37 Table 18 — Dry Bulb Operation without DCV (CO Sensor) — 2 Speed Fan DEMAND OUTSIDE AIR CONTROLLED GOOD TO Y1-I Y2-I FAN SPEED Y1-O Y2-O OCCUPIED UNOCCUPIED VENTILATION (DCV) ECONOMIZE 0-v/Off 0-v/Off MIN POS L Closed NONE 24-v/On 0-v/Off MIN POS L Closed High...
  • Page 38: Enthalpy Settings

    Table 21 — Enthalpy Operation with DCV (CO Sensor) — 2 Speed Fan DEMAND OUTSIDE AIR CONTROLLED GOOD TO Y1-I Y2-I Y1-O Y2-O OCCUPIED UNOCCUPIED SPEED VENTILATION (DCV) ECONOMIZE 0v/Off 0v/Off VENTMIN Closed 24v/On 0v/Off VENTMIN Closed HIGH 24v/On 24v/On VENTMIN Closed 0v/Off...
  • Page 39: Checkout

    ECONOMIZING DUAL ENTHALPY AVAILABLE HIGH LIMIT NOT AVAILABLE SINGLE ENTHALPY P2 (T,RH) (T,RH) TEMPERATURE Fig. 55 — Single Enthalpy Curve Boundaries Table 23 — Single Enthalpy and Dual Enthalpy High Limit Curves POINT P1 POINT P2 ENTHALPY TEMP. DRY TEMP. ENTHALPY HUMIDITY HUMIDITY...
  • Page 40: Low Ambient Control (Factory Option)

    Clearing Alarms arranged for vertical return configurations only. All components necessary for operation are factory-provided and mounted. The Once the alarm has been identified and the cause has been re- unit is factory-configured for immediate smoke detector shutdown moved (e.g. replaced faulty sensor) the alarm can be cleared operation;...
  • Page 41: Step 13 - Adjust Factory-Installed Options

    Unit Without Economizer or Economizer 2 Position Damper 2 Position Damper Fig. 58 — EconoMi$er ® IV Wiring Step 13 — Adjust Factory-Installed Options • Head pressure control • Programmable setback thermostat SMOKE DETECTORS • Electrical/Mechanical thermostat and subbase Smoke detector(s) will be connected at the Controls Connec- •...
  • Page 42: Belt Tension Method

    TENSION FORCE IN BELT (LBS) ners (www.hvacpartners.com). Used Table 2 Fig. 59 — V-Belt Force Label Copyright 2019 Bryant Heating & Cooling Systems Cat. No. 04-53581014-01 Edition Date: 7-19 Printed in U.S.A Form No: II581J-14-04 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 43: Start-Up Checklist

    START-UP CHECKLIST (Remove and use for job file) NOTE: To avoid injury to personnel and damage to equipment or property when com- pleting the procedures listed in this start-up checklist, use good judgment, follow safe practices, and adhere to the safety considerations/information as outlined in preceding sections of this Installation Instructions.
  • Page 44 COMPRESSOR AND OUTDOOR FAN STOP; LSV AND DSV SOLENOIDS DE-ENERGIZED — 10. RESTORE SETPOINTS FOR THERMOSTAT AND HUMIDISTAT REPEAT PROCESS FOR 2 COMPRESSOR SYSTEMS Copyright 2019 Bryant Heating & Cooling Systems Cat. No. 04-53581014-01 Edition Date: 7-19 Printed in U.S.A Form No: II581J-14-04 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Table of Contents