Electrical Data; Wiring - Bryant 619AHB Series Service Manual

High wall ductless system sizes 06 to 36
Hide thumbs Also See for 619AHB Series:
Table of Contents

Advertisement

SG-619AHB-01: Service Manual

ELECTRICAL DATA

HIGH WALL UNIT SIZE
12K
6K
9K
12K
18K
24K
30K
36K
*Permissible limits of the voltage range at which the unit operates satisfactorily.
LEGEND:
FLA - Full Load Amps

WIRING

All wires must be sized per NEC (National Electrical Code) or CEC
(Canadian Electrical Code) and local codes. Use the Electrical Data table
MCA (minimum circuit amps) and MOCP (maximum over current
protection) to correctly size the wires and the disconnect fuse or breakers
respectively.
Per the caution note, only stranded copper conductors with a 600 volt
insulation rating wire must be used.
Recommended Connection Method for Power and Communication
Wiring:
The main power is supplied to the outdoor unit. The field supplied 14/3
stranded wire with ground with a 600 volt insulation rating, power/
communication wiring from the outdoor unit to the indoor unit consists
of four (4) wires and provides the power for the indoor unit.
Two wires are line voltage AC power: connect L1 to terminal (1), N or
L2 to (2), Communication wire to (3), green ground wire to ground
terminal. Refer to the "CONNECTION DIAGRAMS"on page 6 for 115
volt or 208/230 volt connection.
If installed in a high electromagnetic field area (EMF) and
communication issues exist, a 14/2 stranded shielded wire can be used to
replace (2) and (3) (polarity sensitive
indoor unit landing the shield onto the ground in the outdoor unit only.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Table 5 — Electrical Data
INDOOR FAN
V-PH-HZ
115-1-60
208/230-1-60
)
between the outdoor unit and the
FLA
HP
0.20
0.027
0.25
0.027
0.25
0.027
0.25
0.027
Refer to outdoor unit installation instructions –
0.13
0.04
0.5
0.077
0.5
0.077
0.5
0.077
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in damage or
improper operation.
Wires should be sized based on NEC and local codes.
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage
or improper operation.
Be sure to comply with local codes while running wire from
the indoor unit to the outdoor unit.
Every wire must be connected firmly. Loose wiring may
cause the terminal to overheat or result in unit malfunction. A
fire hazard may also exist. Ensure all wiring is tightly
connected.
No wire should touch the refrigerant tubing, compressor or
any moving parts.
Disconnecting means must be provided and shall be located
within sight and readily accessible from the air conditioner.
Connecting cable with conduit shall be routed through the
hole in the conduit panel.
5
MAX FUSE CB AMP
Indoor unit powered by the outdoor unit

Hide quick links: