ABB REL 301 Instruction Manual page 25

Numerical distance relay
Hide thumbs Also See for REL 301:

Advertisement

2
I.L. 40-386.12
Setting
Output Contact 1 Configuration
Output Contact 2 Configuration
Remote Setting Change Enable
Manual Close (settings below
available when Man Close set to
Yes)
*
- Manual Close on HLDB
*
- Manual Close on HBDL
*
- Manual Close if Synchronism
*
- Manual Max Wait Time for a
HLDB, HBDL or Synchronism
Condition
(Man HLDB, HBDL or Sync must
be "yes" to view this setting)
Recloser Enable/Disable
* Settings available only with synchronism check option and when Sync Set? = Yes
2-12
Table 2-6: RECLOSING SETTINGS WITH RANGES (Sheet 4 of 4)
Function
Display
Output 1
Out_1
Output 2
Out_2
Remote Set
Remote Set
Man Close
Man Close
Man HLDB
Man HLDB
Man HBDL
Man HBDL
Man SYNC
Man SYNC
Man Wait
Man Wait
Recloser
Recl Enable
RCP
Display
Displayed
None
In-Progress
HLDB
HBDL
HLDB/HBDL
SYNC
HLDB/HBDL/SYNC
None
Failed Close
HLDB
HBDL
HLDB/HBDL
SYNC
HLDB/HBDL/SYNC
No / Yes
No / Yes
No / Yes
No / Yes
No / Yes
0-99 in 1 Second steps
100-990 in 10 Second steps
Infinite Time (No Time Limit)
Disabled/Enabled
Value
Factory
Default
In-Progress
Failed Close
Yes
No
No
No
No
60 sec
Enabled