ABB REL 301 Instruction Manual page 23

Numerical distance relay
Hide thumbs Also See for REL 301:

Advertisement

2
I.L. 40-386.12
Setting
- Reclose 2 Dead Time
* - Reclose 2 on HLDB
* - Reclose 2 on HBDL
* - Reclose 2 on Synchronism
* - 2 Max Wait Time for a HLDB,
HBDL or Synchronism condition.
(Recl2 HLDB, HBDL or Sync
must be "yes" to view this set-
ting)
Reclosure 3 parameters:
- Reclosure 3 Initiation Method
- Reclose 3 Block
("Recl3" must be set to one of
the setting choices that includes
3RI to view this setting)
- Reclose Dead Time
* - Reclose 3 on HLDB
* - Reclose 3 on HBDL
* - Reclose 3 on Synchronism
* - 3 Max Wait Time for a HLDB,
HBDL or Synchronism condition.
(Recl3 HLDB, HBDL or Sync
must be "yes" to view this set-
ting)
Reclosure 4 parameters:
- Reclosure 4 Initiation Method
- Reclose 4 Block
("Recl4" must be set to one of
the setting choices that includes
3RI to view this setting)
- Reclose 4 Dead Time
* - Reclose 4 on HLDB
* Settings available only with synchronism check option and when Sync Set? = Yes
2-10
Table 2-6: RECLOSING SETTINGS WITH RANGES (Sheet 2 of 4)
Function
Display
Recl2 Time
Recl n Time
Recl2 HLDB
Recl n HLDB
Recl2 HBDL
Recl n HBDL
Recl2 Sync
Recl n Sync
Recl2 Wait
Recl n Wait
(RECI 3)
Recl 3
Recl n Init
Recl3 RB
Recl n RB
Recl3 Time
Recl n Time
Recl3 HLDB
Recl n HLDB
Recl3 HBDL
Recl n HBDL
Recl3 Sync
Recl n Sync
Recl3 Wait
Recl n Wait
(RECI 4)
Recl 4
Recl n Init
Recl4 RB
Recl n RB
Recl4 Time
Recl n Time
Recl4 HLDB
Recl n HLDB
RCP
Display
Displayed
0.01 - 0.99 Step 0.01 sec
1.0 - 99
Step 0.1 sec
10 - 250
Step 1 sec
No / Yes
No / Yes
No / Yes
0 - 99
Step 1 sec
100 - 990 Step 10 sec
No time Limit
(Infinite Time)
52b only /
3RI only /
52b and 3RI /
52b or 3RI
No / Yes
0.01 - 0.99 Step 0.01 sec
1.0 - 9.9
Step 0.1 sec
10 - 250
Step 1 sec
No / Yes
No / Yes
No / Yes
0 - 99
Step 1 sec
100 - 990 Step 10 sec
No time Limit (Infinite Time)
52b only /
3RI only /
52b and 3RI /
52b or 3RI
No / Yes
0.01 - 0.99 Step 0.01 sec
1.0 - 9.9
Step 0.1 sec
10 - 250
Step 1 sec
No / Yes
Value
Factory
Default
3.0 sec
No
No
No
60 sec
52b Only
No
10 sec
No
No
No
60 sec
52b Only
No
30 sec
No