Table 2-6: RECLOSING SETTINGS WITH RANGES (Sheet 3 of 4)
Setting
* - Reclose 4 on HBDL
* - Reclose4 on Synchronism
* - 4 Max Wait Time for a HLDB,
HBDL or Synchronism condition.
(Recl4 HLDB, HBDL or Sync
must be "yes" to view this set-
ting)
Fail Reclose Enable
Fail Reclose Max Close Duration
(Not displayed if Fail Recl? = No)
Close Contact Duration
(Not displayed if Fail Recl? =
Yes)
Reset Duration
Check Hold Input
Maximum Cycle Enable
"Sync Set" must be "No" to view
this setting
Maximum Cycle Time
"Max Cycle" must be "Yes" to
view this setting
Enable
Use of 52aInput
Number of Reclosures to Alarm
Enable
Number of Reclosures to Alarm
(Cum. Recl must Yes to view this
setting)
Breaker Limit Operations:
- Breaker Operation Enable
- Breaker Limit Number
- Breaker Limit Duration
-Breaker Recovery Time
"Br Oper.?" must be "Yes" to
view these settings
* Settings available only with synchronism check option and when Sync Set? = Yes
Function
RCP
Display
Display
Recl4 HBDL
Recl n HBDL
Recl4 Sync
Recl n Sync
Recl4 Wait
Recl n Wait
FailRecl ?
Fail Recl
Fail Time
Fail Time
ClosePulse
ClosePulse
Reset Time
Reset
Hold ?
Hold
MaxCycle ?
MaxCycle
Max Time
Max Time
FollowBr ?
Follow Bkr
52a/Mancls
52a/ManCls
Cum. Recl?
Cum. Recl
Cum. Recl
#Cum. Recl
Br Oper. ?
Bkr Oper
Max Count
Limit Count
Duration
Duration
Recovery
Recovery
Value
Displayed
No / Yes
No / Yes
0 - 99
Step 1 sec
100 - 990 Step 10 sec
No time Limit (Infinite Time)
No / Yes
1 - 99 Step 1 sec
100 - 250 Step 10 sec
0.01 - 0.99 Step 1 sec
1.0 - 2.0
Step 0.1 sec
1 - 99
Step 1 sec
100 - 250 Step 10 sec
No / Yes
No / Yes
1 - 99
Step 1 sec
100 - 990 Step 10 sec
No / Yes
52a, Yes/Manual Close/No, Dis-
abled
No / Yes
0 - 99 Step 1
100 - 990 Step 10
No / Yes
0 - 99
Step 1
100 - 250 Step 10
1 - 99
Step 1 min
100 - 250 Step 10 min
1 - 99
Step 1 min
100 - 250 Step 10 min
2
I.L. 40-386.12
Factory
Default
No
No
60 sec
Yes
10 sec
0.50 sec
15 sec
No
No
990 sec
No
No, Disabled
No
990 recl
No
250 recl
250 min
1 min