User Settings; Phase / Ground Toc Settings (51P / 51G) - GE Multilin MIGII Instruction Manual

Digital protection for electrical machines
Table of Contents

Advertisement

9 RELAY COMMISSIONING

9.23USER SETTINGS

The following pages intend to be useful to register the user settings. They can be used as a guide or template or to record
, in case your company does not provide a proprietary form sheet.
the relay settings
Relay Status
Frequency
ModBus format
Full Load Amps 1A
Full Load Amps 5A
CT Phases
CT Neutral
Minimum time to detect stopped
motor
Motor status detection by 52B
Password
Communications Password
Address
Communication Baudrate
Phase TOC Function
51P Enable
51P Permission to Trip
51P Tap / Pickup Value
51P Curve Type
51P Time Dial
51P Definite Time Delay
Ground TOC Function
51G Enable
51G Permission to Trip
51G Tap / Pickup
51G Curve Type
51G Time Dial
51G Definite Time Delay
GEK-113188A
ENERVISTA MII PC
HMI
GENERAL SETTINGS
GENERAL
RELAY STATUS
Relay Operation
FREQUENCY
Frequency
---
ModBus Format
FLA
Full Load Amps
PHASE CT RATIO
Phase CT Ratio
GROUND CT RATIO
Ground CT Ratio
Minimum time for STOP
Min Stop Time
Supervision by 52B
52 Supervision
---
HMI Password
---
Comm Password
---
Slave Address
---
Comm Baud Rate
ENERVISTA MII PC
HMI
51P Function
F51P
Enable
Enable 51P
51P Trip Permission
Trip Enable51P
51P Pickup
Pickup 51P
51P Curve Type
Curve 51P
51P Time Dial
TD Mult 51P
51P Definite Time
TIME 51P
51G Function
Ground TOC 51G
Enable
Enable 51G
51G Trip Permission
Trip Enable51G
51G Pickup
Pickup 51G
51G Curve Type
Curve 51G
51G Time Dial
TD Mult 51G
51G Definite Time
Def Time 51G
MIGII Digital Protection for Electrical Machines
9.23.1 GENERAL SETTINGS
VALUE RANGE
RDY / DIS
50/60 Hz
INTEL-MOTOROLA
0.1-2.4 A
0.5-10 A
1-4000
1-4000
0-900 s
Yes/No
1 - 255
1 - 255
1 - 255
300, 600, 1200, 2400,
4800, 9600, 19200

9.23.2 PHASE / GROUND TOC SETTINGS (51P / 51G)

VALUE RANGE
Y/N
Y/N
0.1-2.4 FLA (Ph)
INV, V.I., E.I., T.DE, USU
0.05 - 2.00 (IEC curves)
0.5 - 20.0 (ANSI curves)
0 - 99.99 s.
Y/N
Y/N
0.1 - 2.4 In (Gnd)
INV, V.I., E.I., T.DE, USU
0.05 - 2.00 (IEC curves)
0 - 600 s.
9.23 USER SETTINGS
STEP
NA
NA
NA
0.01
0.01
1
1
1
NA
1
1
NA
STEP
NA
NA
0.01
NA
0.01
0.01
0.01 s.
NA
NA
0.01 In (Gnd)
NA
0.01
0.01 s.
9-27
9

Advertisement

Table of Contents
loading