9 RELAY COMMISSIONING
Thermal Image (49)
F49 Enabling
Permission to Trip
49 Tap / Pickup (on FLA)
Overload Percent Alarm
Heating Time Constant τ1
Cooling Time Constant τ2
K1 Constant
Number starts (66)
66 Enabling
66 Permission to Operate
No. Starts per hour
Block reset time (STOP-START) Restart Time
Restricted Ground Differential
87R Enabling
87R Permission to Trip
Differential sensitivity (S)
87R Time Delay
87R Percentage slope
*For models with sensitive ground, function 87R is not applied.
GEK-113188A
ENERVISTA MII PC
HMI
49 Function
THERMAL MODEL 49
Enable 49
Enable
49 Trip Permission
Trip Enable49
49 Pickup
Pickup 49
49 Alarm Level
Alarm Level 49
T1
Heat Time 49
T2
Cool Time 49
K1
Constant K1
ENERVISTA MII PC
HMI
66 Function
NUMBER STARTS 66
Enable 66
Enable 66
66 Oper. Permission
Operate 66
No. Starts
Number Starts
Time to Restart
ENERVISTA MII PC
HMI
*
87R Function
F87R
Enable 87R
Enable 87R
87R Trip Permission
Trip Enable 87R
S 87R
Pickup
T
Delay 87R
K
K 87R
MIGII Digital Protection for Electrical Machines

9.23.7 THERMAL IMAGE SETTINGS (49)

VALUE RANGE
Y/N
Y/N
0.1 - 2.4 FLA
70% - 100% ITH
3 - 600 min
1 - 6 times τ1
1 – 8

9.23.8 MAXIMUM NUMBER OF STARTS (66) (MIGII Q)

VALUE RANGE
Y/N
Y/N
0-10
0 – 100 min
9.23.9 (87R SETTINGS (MIGII P)
VALUE
RANGE
Y/N
Y/N
0.01 – 0.3 In
0.0 - 600 s.
0.1 – 1.2
9.23 USER SETTINGS
STEP
NA
NA
0.01
1%
1 min
1
1
STEP
NA
NA
1
1
STEP
NA
NA
0.01 In
0.01 s.
0.1
9-29
9