5 SETTINGS

5.3ADVANCED SETTINGS

MENU
MAIN SETTINGS
ADVANCED SETTINGS
GENERAL ADVANCED
NOTE ABOUT THE TRIP MIN TIME SETTING:
This setting indicates the time during which the tripping contact will remain closed as a minimum in
case of fault. If the fault persists for a longer time than the set value, the tripping contact will remain
closed and will be opened immediately after the fault is cleared, while if the fault is shorter than the
set time, the relay will maintain the contact closed for this set time.
GEK-113188A
ADVANCED SETTINGS
GENERAL ADVANCED
ENTER
Setting Group
GENERAL ADVANCED
Trip Min Time
MIGII Digital Protection for Electrical Machines
5.3 ADVANCED SETTINGS
Range: 1 - 2
Default: 1
Range: 50-300 ms
Default: 200 ms
5.3.1